Inspection
Inspection Details
Equipment ID
10718
10718
Inspection Date
3/4/2020
3/4/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Jeffrey VanZant
Jeffrey VanZant
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
FR 20 R 20
FR 20 R 20
External ID
48b7b9f2-67b0-46ef-9a0d-26edc318f9bb
48b7b9f2-67b0-46ef-9a0d-26edc318f9bb
Location
CMC Auditorium
1900 GRAND AVE, CARTHAGE, MO
Phone: (417) 358-7787
1900 GRAND AVE, CARTHAGE, MO
Phone: (417) 358-7787
Owner
Congregation of the Mother of Coredemptrix
1900 GRAND AVE, CARTHAGE, MO 64836-3500
1900 GRAND AVE, CARTHAGE, MO 64836-3500
Billing
Attn: Congregation of the Mother of Coredemptrix
1900 GRAND AVE, CARTHAGE, MO 64836-3500
1900 GRAND AVE, CARTHAGE, MO 64836-3500
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | all non elevator items must be removed from machine room | 9/1/2022 |
| conversion | conversion | n/a | No | No | needs current certificate posted in frame in machine room | 9/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current state certificate posted in machine room | 9/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 8.6.1.6.5 fire extinguisher hasn't been checked since 2014 | 9/1/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | all non elevator items need to be removed from machine room | 9/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | needs current certificate posted | 9/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Cab forced ventilation fan shall work | 9/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Car Gate switch shall not register “closed” at greater than 2” open. (REINSPECTION REQUIRED) | 4/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired) | 9/1/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non-elevator related items shall not be stored in Machine Room. (vacuums, signs, etc) | 9/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Car Gate switch shall not register “closed” at greater than 2” open. (REINSPECTION REQUIRED) | 4/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 2021&2022: G(1)/1.14.1/1001.2(a)(14) Cab forced ventilation fan shall work (very noisy, repair or replace) | 9/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing "Do not use elevator in case of fire" Signage on multiple floors | 9/1/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non-elevator related items shall not be stored in Machine Room. (Shiny wrapped boxes, dog kennel, etc.) This room is for the elevator ONLY. | 9/1/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide operational telephone in elevator cab | 5/1/2023 |