Inspection
Inspection Details
Equipment ID
4740
4740
Inspection Date
2/5/2020
2/5/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
310
310
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
a092f7bf-d208-4ffb-96f7-49e9db282d78
a092f7bf-d208-4ffb-96f7-49e9db282d78
Location
Electro Savings Credit Union
1805 CRAIGSHIRE RD, SAINT LOUIS, MO
Phone: (314) 434-6470
1805 CRAIGSHIRE RD, SAINT LOUIS, MO
Phone: (314) 434-6470
Owner
Electro Savings Credit Union
1805 CRAIGSHIRE RD, SAINT LOUIS, MO 63146-4005
1805 CRAIGSHIRE RD, SAINT LOUIS, MO 63146-4005
Billing
Attn: Electro Savings Credit Union
1805 CRAIGSHIRE RD, SAINT LOUIS, MO 63146-4005
1805 CRAIGSHIRE RD, SAINT LOUIS, MO 63146-4005
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Recommend expired battery in door restrictor control box be changed. | 8/27/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In cab emergency telephone shall work with 24/7 support. | 3/1/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 6/24/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 6/24/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The light fixture switch in the pit shall be provided and accessible from the pit access door. The pit light switch is approximately 64 inches from the door. | 6/24/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency bell did not work when the 110v disconnect was de-energized. The in car emergency bell shall be operational. | 2/2/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 8/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Firefighters phase one instructions shall be posted near the phase one key switch in the hallway at the egress floor. | 8/6/2024 |