Inspection
Inspection Details
Equipment ID
5122
5122
Inspection Date
3/6/2020
3/6/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Richard DuFrenne
Richard DuFrenne
Relief Valve Pressure
410
410
Slide
Governor Rope Pull
Door Closing Force
30/30
30/30
External ID
af9c21e7-027e-4fb5-b6cf-17570ddcc701
af9c21e7-027e-4fb5-b6cf-17570ddcc701
Location
Alexian Court Apartments
2636 CHIPPEWA ST, SAINT LOUIS, MO
Phone: (314) 771-5604
2636 CHIPPEWA ST, SAINT LOUIS, MO
Phone: (314) 771-5604
Owner
Attn: UNK
National Church Residences
2636 CHIPPEWA ST, SAINT LOUIS, MO 63118
Phone: (314) 771-5604
National Church Residences
2636 CHIPPEWA ST, SAINT LOUIS, MO 63118
Phone: (314) 771-5604
Billing
Attn: Alexian Court Apartments
National Church Residences
2636 CHIPPEWA ST, SAINT LOUIS, MO 63118
Phone: (314) 771-5604
Email: 0931@nationalchurchresidences.org
National Church Residences
2636 CHIPPEWA ST, SAINT LOUIS, MO 63118
Phone: (314) 771-5604
Email: 0931@nationalchurchresidences.org
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Remove emergency lights in car | 10/24/2018 | ||
conversion | conversion | n/a | Remove oil from pit floor | 10/24/2018 | ||
conversion | conversion | n/a | Remove oil from pit floor | 10/24/2018 | ||
conversion | conversion | n/a | Repair emergency light in car | 10/24/2018 | ||
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Repair Phase 2 Fire Service in car on hold will not over ride door close button | 4/15/2019 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Need a maintenance control program on site posted on controller asap | 11/3/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | The emergency phone shall be operational and code compliant. The answering service can not be heard. | 12/29/2022 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | Clear the entrance to the machine room. Access to the machine space shall maintained in a clear and unobstructed manner. | 5/8/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Exhaust fan is missing cover in machine room. Replace the fan cover. | 5/8/2023 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Up to date operating certificate is required in the machine room. | 5/8/2023 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Guard machine room light. | 5/8/2023 | ||
MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 (Re-Inspection) | x | Packing on jack is leaking. Take corrective action as needed. | 3/28/2023 | |
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Fire service phase 1 is working, but will not transfer to phase 2. Take corrective action as needed. | 3/28/2023 | |
MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 (Re-Inspection) | x | Packing on jack is leaking. Take corrective action as needed. | 5/8/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Two-way communications device shall work. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Stop switch shall be wired to alarm for audible notification (after 1984). Front COP stop does not sound alarm. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Car door restrictor shall work at all floors. Multiple brackets missing. | ||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | x | Cab lighting shall be a dedicated circuit. Currently on the same circuit as second floor hallway lighting/receptacles. NEC 620-22 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door shall be self-closing and self-locking. | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Fire service testing shall be documented monthy. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Front door close button does not work. |