Inspection
Inspection Details
Equipment ID
10832
10832
Inspection Date
2/7/2020
2/7/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
158b7774-5625-403d-971d-cbcd5a123ecc
158b7774-5625-403d-971d-cbcd5a123ecc
Location
Ranken Technical College
4431 FINNEY AVE, SAINT LOUIS, MO
Phone: (314) 267-2865
4431 FINNEY AVE, SAINT LOUIS, MO
Phone: (314) 267-2865
Owner
Ranken Technical College
4431 FINNEY AVE, SAINT LOUIS, MO 63113-2811
4431 FINNEY AVE, SAINT LOUIS, MO 63113-2811
Billing
Attn: Ranken Technical College
Steve Hartege
4431 FINNEY AVE, SAINT LOUIS, MO 63113-2811
Steve Hartege
4431 FINNEY AVE, SAINT LOUIS, MO 63113-2811
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate in the elevator machine room. | 4/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. Could not establish 2 way communication. | 2/7/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide a code compliant MCP including onsite documents. | 4/28/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 4/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency alarm bell shall be operational. | 10/18/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | MCP evacuation procedures are required on-site. | 5/5/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 8/18/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Car door restrictor shall work at all floors. | 5/17/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120v power. | 5/17/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. | 5/17/2024 |