Inspection
Inspection Details
Equipment ID
18879
18879
Inspection Date
1/28/2020
1/28/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
ddf438a2-5d87-49d4-8193-6d6131b9bd9c
ddf438a2-5d87-49d4-8193-6d6131b9bd9c
Location
Ventana Lofts
1635 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 371-0035
1635 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 371-0035
Owner
Attn: Mike McRogerts
Mike McRogerts
104 N Armour, North Kansas City, MO 64116
Phone: (000) 000-0000
Mike McRogerts
104 N Armour, North Kansas City, MO 64116
Phone: (000) 000-0000
Billing
Attn: Ventana Lofts
Bogen Lofts Accounts Payable
1207 Washington Ave, SAINT LOUIS, MO 63103
Phone: (314) 241-6644
Email: manager@thebogen.com
Bogen Lofts Accounts Payable
1207 Washington Ave, SAINT LOUIS, MO 63103
Phone: (314) 241-6644
Email: manager@thebogen.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | x | Car door restrictor shall work. | 4/23/2019 | |
A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | x | 8.4.10.12(c) - Counterweight derailment does not work. | 4/23/2019 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | In car emergency telephone shall work. | 4/23/2019 | |
A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | x | x | The car door restrictor shall be operational. | 1/30/2020 |
A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | x | The car gate switch shall be operational. | 1/30/2020 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | The pit light shall be operational. | 3/6/2023 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Clean the pit of dirt and debris. | 3/6/2023 | ||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | x | Test the keyed stop switch in Phase 1. | 1/30/2020 |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Maintain a monthly fire service testing log for Phase 1 & 2 fire service. | 3/6/2023 | ||
A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | x | 8.4.10.1.2(c) - Counterweight derailment shall be operational. | 1/30/2020 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | The pit light shall be operational. | 3/6/2023 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Clean the pit of dirt and debris. | 3/6/2023 | ||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | x | Test the keyed stop switch in Phase 1. | 1/27/2021 |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Maintain a monthly fire service testing log for Phase 1 & 2 fire service. | 3/6/2023 | ||
A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | x | 8.4.10.1.2(c) - Counterweight derailment shall be operational. | 1/27/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | The pit shall be kept clean. Clean the pit. | 2/2/2023 |