Inspection
Inspection Details
Equipment ID
16889
16889
Inspection Date
2/24/2020
2/24/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Mark Brown
Mark Brown
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
307f8554-af0f-4bf8-8ea3-3bca58b0ab8e
307f8554-af0f-4bf8-8ea3-3bca58b0ab8e
Location
St. Louis Busch Stadium
700 CLARK AVE, SAINT LOUIS, MO
Phone: (314) 345-9404
700 CLARK AVE, SAINT LOUIS, MO
Phone: (314) 345-9404
Owner
Attn: Hope Baker
St. Louis Cardinals LLC
700 CLARK AVE, SAINT LOUIS, MO 63102
Phone: (314) 345-9309
Email: hbaker@cardinals.com
St. Louis Cardinals LLC
700 CLARK AVE, SAINT LOUIS, MO 63102
Phone: (314) 345-9309
Email: hbaker@cardinals.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair the bottom demarcation light. | 1/7/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | comb impact guides guides ar rushed and need to be tested to insure proper impact calibration. | 2/18/2019 |
| A17.1-1996 : Escalators | 7.9 - Steps and upthrust device | 802.5 | No | No | Replace broken step demarcation strip. | 3/29/2023 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 1206.6 | No | No | Comb impact guides are rusted. Pressure test on tripping pressure needed. Reinspect within 30 days. | 3/29/2023 |
| A17.1-1996 : Escalators | 7.16 - Ceiling intersection guards | 802.3g | No | No | Replace wrong ceiling intersection guards with correct ones. | 7/2/2020 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 802.6 | No | No | Replace broken step demarcations. | 7/2/2020 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Top demarcation light does not work | 7/21/2023 |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3.3 | No | No | Step/skirt index exceeded the allowed amount of .25 | 7/21/2023 |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.1 | No | No | Both handrails need replaced due to cracks causing pinching hazards | 7/21/2023 |
| A17.1-1996 : Escalators | 7.16 - Ceiling intersection guards | 802.3g | No | No | A ceiling intersection guard has been broken and shall be replaced. | 4/19/2024 |
| A17.1-2016 : Elevators | 7.19 - Maintenance records | 8.6.1.4.1(a)(1) | No | No | Record maintenance, call backs, repairs,& testing in MCP and give location of MCP on controller | 8/26/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(d) | No | No | Record graph of Step/Skirt indexing for 2025 and place in MCP for permanent records | 8/26/2025 |