Inspection
Inspection Details
Equipment ID
13115
13115
Inspection Date
2/24/2020
2/24/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
28
28
External ID
bdd153a7-f58a-4fd2-acab-901305c5353d
bdd153a7-f58a-4fd2-acab-901305c5353d
Location
AT & T- St. Louis
ONE AT & T CENTER, ST. LOUIS, MO
Phone: (314) 235-9992
ONE AT & T CENTER, ST. LOUIS, MO
Phone: (314) 235-9992
Owner
Attn: Colliers International
Colliers International
701 Market St, Ste 270, St. Louis, MO 63101
Phone: (314) 241-1245 Ext: 127
Email: Bridget.Reich@colliers.com
Colliers International
701 Market St, Ste 270, St. Louis, MO 63101
Phone: (314) 241-1245 Ext: 127
Email: Bridget.Reich@colliers.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | Repair car door restrictor. | 7/9/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Clean debris from pit. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | Fire extinguisher needs to be serviced. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | x | Perform unintended motion test. 8.6.4.19.11 (c) | 4/20/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone is not working. | 5/12/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Machine room needs to be cleaned. | 5/31/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | The pit shall be kept clean and dry. Remove water from pit floor. | 5/31/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | Emergency lights are not working. | 5/12/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.2 Minimum Illumination | The lights in the car are not all working. There is some water damage. | 5/31/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | Top of car needs to be cleaned. | 5/31/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | x | Need to test emergency power. | 5/12/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10 Emegency Operation and Signaling Devices | x | Earthquake protection is not working. | 5/12/2023 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Not able to finish inspection. Did not test the brakes, slide, crash the buffers/car & counterweights, safeties & governor, the door restrictor, 125% weight test. | 5/12/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Elevator currently not able to operate on emergency power. Water damage in the building damaged the transfer panel. Once fixed emergency power will need to be tested. |