Inspection
Inspection Details
Equipment ID
13376
13376
Inspection Date
2/11/2020
2/11/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Bryan Hesskamp
Bryan Hesskamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
13b73bbd-ab31-4ca7-bb60-d0015d97e52b
13b73bbd-ab31-4ca7-bb60-d0015d97e52b
Location
Soldiers Memorial
1315 CHESTNUT ST, SAINT LOUIS, MO
Phone: (314) 746-4599
1315 CHESTNUT ST, SAINT LOUIS, MO
Phone: (314) 746-4599
Owner
Attn: Soldiers Memorial Military Museum
Soldiers Memorial Military Museum
5700 LINDELL BLVD, PO Box 775460 ,SAINT LOUIS, MO 63112
Phone: (314) 454-3119
Email: AP@mohistory.org
Soldiers Memorial Military Museum
5700 LINDELL BLVD, PO Box 775460 ,SAINT LOUIS, MO 63112
Phone: (314) 454-3119
Email: AP@mohistory.org
Billing
Attn: Jefferson Memorial
Soldiers Memorial Military Museum
1315 Chestnut St, PO Box 775460 ,SAINT LOUIS, MO 63112
Phone: (314) 454-3119
Email: AP@mohistory.org
Soldiers Memorial Military Museum
1315 Chestnut St, PO Box 775460 ,SAINT LOUIS, MO 63112
Phone: (314) 454-3119
Email: AP@mohistory.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | Provide smoke detector(s) in secondary machine space and provide testing of smoke detectors. | 4/15/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | Provide heat detectors in secondary machine space and provide testing of heat detectors. | 4/15/2019 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | The panel designation and breaker numbers feeding the main line disconnect shall be indicated on the disconnect. | 4/15/2019 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | The panel designation and breaker numbers feeding the 110v disconnect shall be indicated on the disconnect. | 4/15/2019 |
| A17.1-1996 : Elevators | 2.40 - Maintenance Records | 210.1d Inspection Operation. | No | No | Provide MCP in machine room. | 4/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Label the disconnects with the source panel location, panel designation and breaker number. | 4/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational on auxiliary power. | 5/13/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.4 Protection of Light Bulbs and Tubes | No | No | In car lighting shall be externally guarded or coated to contain broken glass in case the bulb or tube accidentally breaks. | 5/13/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door restrictor shall be operational. | 5/13/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | The fire extinguisher in the elevator machine room is expired and shall be replaced or serviced. | 5/13/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/13/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.4 Protection of Light Bulbs and Tubes | No | No | In car lighting shall be externally guarded or coated to contain broken glass in case the bulb or tube accidentally breaks. | 5/13/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/22/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/22/2022 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 3/22/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 3/22/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Fire service testing shall be documented monthly. | 8/27/2025 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Non-elevator related items shall not be stored in the machine room. | 8/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Remote set/reset function of governor does not work. | 8/27/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | No one answered the emergency phone. A two-way communications means between the car and a location staffed by authorized personnel shall be provided. | 4/4/2025 |
| A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 1001.2(b)(28) | Yes | No | Remote set/reset function of governor does not work. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Hoist Ropes appear dry and showing “rouge”. Ropes shall be cleaned and lubricated per OEM recommendations. |