Inspection
Inspection Details
Equipment ID
19917
19917
Inspection Date
6/11/2018
6/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
Location
Arrowhead Stadium
#1 Arrowhead Drive, Kansas City, MO
Phone: (816) 921-3600
#1 Arrowhead Drive, Kansas City, MO
Phone: (816) 921-3600
Owner
Jackson County Sports Authority
#1 Arrowhead Drive, Kansas City, MO 64129
#1 Arrowhead Drive, Kansas City, MO 64129
Billing
Attn: Jackson County Sports Authority
#1 Arrowhead Drive, , MO 64129
#1 Arrowhead Drive, , MO 64129
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | hoistway door identification numbering on the top two landings does not match the jamb braille, redo the door numbering to match the jamb braille | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | the top two floor are numbered 7 and 8 on the hoistway side while the jambs are numbered 8 and 9. change the hoistway number to match the jamb number to avioid confusion | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | No | No | repair top landing hoistway access keyswitch, it would not run the elevator in the down direction | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 8.11.2.1.1(h) | Yes | No | adjust the door close to below 30lbf, measured over 35lbf | 5/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | the top two landing the hoistway side numbers do not match the jamb numbers, renumber the hoistway side to match the jamb numbers | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | No | No | repair the top landing hoistway access, could not run the elevator down | 7/28/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency lights did not come on, the alarm bell worked, replace the batteries, verify the battery charger is functioning. | 6/6/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | No | No | The Maintenance Control Program On-Site documents are not in the machine room. | 7/28/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/28/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | Did not have a written record of the maintenance performed on this elevator in the machine room. | 7/28/2025 |