Inspection
Inspection Details
Equipment ID
21384
21384
Inspection Date
6/8/2018
6/8/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Relief Valve Pressure
1500
1500
Slide
Governor Rope Pull
Door Closing Force
29F/29R
29F/29R
External ID
Location
Hamilton Elementary School
5819 Westminister Place, St. Louis, MO
Phone: (314) 385-4767
5819 Westminister Place, St. Louis, MO
Phone: (314) 385-4767
Owner
St. Louis Public Schools
801 North 11th St., St. Louis, MO 63101
801 North 11th St., St. Louis, MO 63101
Billing
Attn: St. Louis Public School
PO Box 423, , MO 64601
PO Box 423, , MO 64601
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 6/23/2022 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | Failed Cat 5 OSV test. Re-inspection required | 11/10/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Yes | No | Elevator was malfunctioning and could not get car to overspeed to test OSV, inspection failed. Needs repaired. Re-inspection required | 2/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace broken top left guide shoe insert. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace worn top left guide shoe insert | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace worn top left guide shoe insert | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace worn out top left guide shoe insert | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, phone line appears to have no power. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the written MCP shall be kept in the machine room for each unit | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test is incomplete, need to perform relief valve pressure test of hydraulic system and slack rope car safety with no load in the car. Re-inspection required |