Inspection
Inspection Details
Equipment ID
12901
12901
Inspection Date
3/16/2020
3/16/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
11
11
Governor Rope Pull
95/720
95/720
Door Closing Force
29
29
External ID
f670ff28-688a-485d-aad9-50159b8650d6
f670ff28-688a-485d-aad9-50159b8650d6
Location
Drury Hotels
3800 STATE ROUTE 141, ARNOLD, MO
Phone: (636) 287-3111
3800 STATE ROUTE 141, ARNOLD, MO
Phone: (636) 287-3111
Owner
Attn: UNK
Drury Hotels
721 EMERSON RD STE 200, SAINT LOUIS, MO 63141
Phone: (000) 000-0000
Drury Hotels
721 EMERSON RD STE 200, SAINT LOUIS, MO 63141
Phone: (000) 000-0000
Billing
Attn: UNK
Drury Hotels
3800 STATE ROUTE 141, ARNOLD, MO 63010
Phone: (000) 000-0000
Email: pat.travers@druryhotels.com
Drury Hotels
3800 STATE ROUTE 141, ARNOLD, MO 63010
Phone: (000) 000-0000
Email: pat.travers@druryhotels.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.16 - Traveling cables and junction boxes | 2.8.1 | No | No | Traveling cable is split open and needs to be replaced. | 11/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency light. | 4/28/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service needs to be tested due to Car #1 being shut down for broken car operating panel. Re-inspection required | 12/13/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of current Missouri Operating Certificate needs to be displayed in machine room | 2/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance control program needs updated | 2/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Door restrictor is missing parts. Replace same. Reinspection required within 30 days. | 2/21/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working | 2/21/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a machine room, hoistway, and pit inspection was performed. A full inspection shall be performed before the Category 5 testing is completed. Reinspection is required. | 2/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | There are multiple car call stations not operating and shall be repaired/replaced. | 2/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Unable to communicate with emergency personnel over phone. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | There are multiple car call stations not operating and shall be repaired/replaced. |