Inspection
Inspection Details
Equipment ID
17193
17193
Inspection Date
3/2/2020
3/2/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
79371751-331a-4c36-b706-54b8534d57c1
79371751-331a-4c36-b706-54b8534d57c1
Location
St. Louis Busch Stadium
700 CLARK AVE, SAINT LOUIS, MO
Phone: (314) 345-9404
700 CLARK AVE, SAINT LOUIS, MO
Phone: (314) 345-9404
Owner
Attn: Hope Baker
St. Louis Cardinals LLC
700 CLARK AVE, SAINT LOUIS, MO 63102
Phone: (314) 345-9309
Email: hbaker@cardinals.com
St. Louis Cardinals LLC
700 CLARK AVE, SAINT LOUIS, MO 63102
Phone: (314) 345-9309
Email: hbaker@cardinals.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | No | No | Phone light indicator bezel in elevator cab is broken. Repair | 3/29/2023 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Replace burnt out lights in elevator machine room. | 5/3/2023 |
| A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | Yes | No | Governor rope pull through force is 700 lbs. Govenor nameplate is 400 lbs maximum. Replace/repair. | 12/6/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 5/3/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | All fire service keys for elevators in one building shall be keyed alike. Re-inspection required | 3/10/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 5/3/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car shall work. Re-inspection required | 5/6/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Overspeed governor rope is damaged and has breaks, need to replace rope. Red-tagged, Re-inspection required | 5/6/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Light fixture in machine room has two burned out bulbs, replace same to provide at least 10 fc illumination at floor | 8/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car shall work. | 3/4/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Light fixture in machine room has burned out bulbs. Replace same to provide at least 10 fc illumination at floor. | 8/26/2025 |