Inspection
Inspection Details
Equipment ID
24039
24039
Inspection Date
2/19/2020
2/19/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
Scott Breihan
Scott Breihan
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
53bb2aed-497a-44a9-a032-cc156a11d592
53bb2aed-497a-44a9-a032-cc156a11d592
Location
Centene Claims
1350 AIRPARK DR, FARMINGTON, MO
Phone: (314) 422-7350
1350 AIRPARK DR, FARMINGTON, MO
Phone: (314) 422-7350
Owner
Attn: Mike Debert
Centene Corporation
7711 CARONDELET AVE, CLAYTON, MO 63105
Phone: (314) 991-1158
Email: mdebert@centene.com
Centene Corporation
7711 CARONDELET AVE, CLAYTON, MO 63105
Phone: (314) 991-1158
Email: mdebert@centene.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work with 24/7 support. | 8/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 8.11.2.1.1(h) | Yes | No | Door closing force shall be tested and recorded. | 8/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Provide testing of emergency brake. | 8/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | Yes | No | Provide lobby warning placards on 2nd and 3rd floors. | 8/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 8.11.2.1.4(l) | Yes | No | Testing of emergency power shall be conducted on the car with weights. | 8/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | The sump pump shall be tested and a sump pump cover shall be installed. | 8/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.12 - Car enclosure | 8.11.2.1.1(l) | Yes | No | Provide a finished floor in the elevator car. | 8/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | All phases of fire service and and initiating devices shall be tested. | 8/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | Yes | No | 2.11.10.2/IBC - Provide permanent lobby lighting on all floors. | 8/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | The pit shall be cleaned. | 8/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | Yes | No | 2.11/NEC - Provide feeder locations (Main and 110V) on controller disconnect. | 8/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency power shall be tested. | 2/19/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate. | 3/27/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate. | 3/27/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency power operation of the elevator was tested, but did not work properly. Emergency power operation of the elevator shall be operational and shall be tested for compliance. | 11/18/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Replace any missing fire tabs on hoistway doors. | 12/2/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service testing must be documented monthly. | 12/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace faded/unreadable Phase 1 switch bezel. | 12/2/2024 |