Inspection
Inspection Details
Equipment ID
12869
12869
Inspection Date
6/1/2018
6/1/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Relief Valve Pressure
Slide
28"
28"
Governor Rope Pull
150 / 730
150 / 730
Door Closing Force
24
24
External ID
Location
Merchandise Mart Apartments
1000 Washington Ave, St. Louis, MO
Phone: (314) 436-6800
1000 Washington Ave, St. Louis, MO
Phone: (314) 436-6800
Owner
Mermart LLC
911 Washington Ave, Suite 400, St. Louis, MO 63101
911 Washington Ave, Suite 400, St. Louis, MO 63101
Billing
Attn: Mermart LLC
1000 Washington Ave, , MO 63101
1000 Washington Ave, , MO 63101
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 11/7/2023 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | Yes | No | There is a top and bottom guide roller on the counterweight that has deteriorated and shall be replaced. | 7/29/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - The fireman service phase I key switch housing is damaged and shall be replaced. Reinspection required. | 7/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The signage for “In Case of Fire” is missing on a number of landings. Install signage that conforms to the building code this elevator was installed to meet. | 11/7/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove non elevator related materials from machine room | 11/7/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit shall be cleaned | 11/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace worn guide rollers / shoes on the top of counterweight | 11/7/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 8/21/2023 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light in the cab does not work on emergency 110v power | 11/12/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | One of the suspension ropes has frayed/broke. Ropes shall be replaced and reinspected | 11/12/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Provide testing of the elevator on emergency power. | |
| A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1002.2g | Yes | No | Provide testing of the elevator emergency power selector switch, located in the Fire Command Room. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Provide current year tested fire extinguisher in the elevator machine room. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post Phase I instructions near the f/f switch in the lobby. |