Inspection
Inspection Details
        Equipment ID
13666
    13666
        Inspection Date
2/18/2020
    2/18/2020
        Inspection Type
Annual Inspection
    Annual Inspection
        Inspector Name
Edward Balsat
    Edward Balsat
        Mechanic Name
Phillip Moise, Jr.
    Phillip Moise, Jr.
        Relief Valve Pressure
          
    
    
        Slide
NA
    NA
        Governor Rope Pull
NA
    NA
        Door Closing Force
22
    22
        External ID
225dc0a1-955a-4868-b8eb-65582a028320
225dc0a1-955a-4868-b8eb-65582a028320
Location
            Kiener West Garage
604 PINE ST, SAINT LOUIS, MO
Phone: (314) 241-4262
                                            
    604 PINE ST, SAINT LOUIS, MO
Phone: (314) 241-4262
Owner
            Inter Park Holdings LLC
100 S 9TH ST, SAINT LOUIS, MO 63102-1124
                                            
    100 S 9TH ST, SAINT LOUIS, MO 63102-1124
Billing
                    Attn: Inter Park
100 S 9TH ST, SAINT LOUIS, MO 63102-1124
        
    100 S 9TH ST, SAINT LOUIS, MO 63102-1124
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date | 
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Governor rope is severely rusted and shall be replaced. | 10/2/2018 | |
| conversion | conversion | conversion - reinspect | x | Cab emergency telephone does not work and shall be repaired and tested. | 10/2/2018 | |
| conversion | conversion | n/a | Hoistway door interlock covers are missing on ground, 1st, 2nd, 5th, & 6th floor landings and shall be replaced. | 5/5/2020 | ||
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | x | x | A category 5 inspection is required. | 2/18/2020 | 
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Phase 1 and Phase 2 key switches shall be keyed the same. | 2/18/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Sheave seals worn and leaking. Repair or replace as needed. | 5/5/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | The pit shall be kept clean and dry. | 5/5/2020 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | In cab emergency telephone shall work with 24/7 support. | 2/18/2020 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post the current state operating certificate in the elevator machine room. | 5/5/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Interlocks at floors 2 & 5 shall have covers installed. | 5/5/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | The pit lighting shall be operational. | 5/5/2020 | ||
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | x | x | A category 5 full load test is due. Unit will be modernized in March/April. Deputy Chief Gus Guadamuz approved delay in Category 5 test until MOD. | 7/27/2020 | 
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | x | Machine room wiring shall be enclosed. | 9/30/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | x | All wireway and electrical device covers must be installed. | 9/30/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | x | Temporary wiring must be removed. | 9/30/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | x | Equipment in the machine room not being used in conjunction with the function or use of the elevators shall be removed. | 9/30/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | x | 2.4.5 - A data plate complying with 2.16.3.3 permanently and securely attached shall be provided in the pit, in the vicinity of the counterweight buffer, indicating the maximum designed counterweight runby. | 9/30/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | x | The machines, controller, governor, isolation transformers, and disconnects shall have an identification number or letter painted or engraved, or securely attached, corresponding to the elevator they serve, and shall be a minimum of 2" in height. | 9/30/2020 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Governors need to be spun and pullout/pull thru test must be performed. | 7/11/2025 |