Inspection
Inspection Details
Equipment ID
2888
2888
Inspection Date
5/24/2018
5/24/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
NA
NA
External ID
2888
2888
Location
Arsenal Pump Station
3000 S Wharf St, St. Louis, MO
Phone: (636) 768-6200
3000 S Wharf St, St. Louis, MO
Phone: (636) 768-6200
Owner
Metropolitan Sewer District STL
2350 Market St, St. Louis, MO 63103-2555
2350 Market St, St. Louis, MO 63103-2555
Billing
Attn: Metropolitan Sewer District
2350 Market St, , MO 63103-2555
2350 Market St, , MO 63103-2555
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current state certificate in themachine room | 6/2/2020 |
| conversion | conversion | n/a | No | No | Prove handel on top floor hoistway door | 6/2/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | Repair phone in car | 6/6/2019 |
| conversion | conversion | n/a | No | No | Provide missing access panel to machine space | 6/2/2020 |
| conversion | conversion | n/a | No | No | Install guard on light in car | 6/2/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 4/23/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)6 | No | Yes | Hoistway doors shall comply with A17.1 1978 Part XV | |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)9 | No | No | A car door shall be provided at each entrance, at least 7' high. The door or gate shall be provided with interlocks. | 6/2/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance records and electrical prints shall be provided. | 6/2/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Maintenance shall comply with A17.1 2004 | 6/2/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car safety pan needs to be non-combustible material. | 6/2/2020 |