Inspection
Inspection Details
Equipment ID
9078
9078
Inspection Date
2/17/2020
2/17/2020
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Vincent Langendoerfer
Vincent Langendoerfer
Relief Valve Pressure
Slide
17" @ 275 FPM
17" @ 275 FPM
Governor Rope Pull
360/500
360/500
Door Closing Force
20
20
External ID
f642bbb1-d62e-48e2-a4cb-a46d2575e507
f642bbb1-d62e-48e2-a4cb-a46d2575e507
Location
Terrace Lofts
1300 CONVENTION PLZ, SAINT LOUIS, MO
Phone: (314) 621-7800
1300 CONVENTION PLZ, SAINT LOUIS, MO
Phone: (314) 621-7800
Owner
Attn: Terraceloftsrobert LLC & Terraceloft LLC & Terraceloftsrst LLC
Terraceloftsrobert LLC & Terraceloft LLC & Terraceloftsrst LLC
393 N Euclid, ste 300, St. Louis, MO 63108
Phone: (314) 761-7067 Ext: 135
Email: steve@redbrickstl.com
Terraceloftsrobert LLC & Terraceloft LLC & Terraceloftsrst LLC
393 N Euclid, ste 300, St. Louis, MO 63108
Phone: (314) 761-7067 Ext: 135
Email: steve@redbrickstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperable emergency phone. | 2/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Yes | No | Machine room wiring shall be enclosed. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Yes | No | The machine room lighting shall not be less than 19fc at the floor level. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | Yes | No | An ABC type fire extinguisher shall be provided in the elevator machine room. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.1 - Car platform guard | 8.11.2.1.4(a) | Yes | No | Car platform guard shall be 48". | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Yes | No | Provide temperature and humidity control. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Provide counterweight runby signage. Signage shall be 1" stamped, etched, or cast lettering. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | Yes | No | Seal all machine room penetrations. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | Yes | No | Seal all hoistway penetrations. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | Yes | No | Provide code compliant pit lighting. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | Yes | No | Adjust bottom hoistway access. | 7/6/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/16/2023 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 3/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher is still out of date | 3/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | The fire extinguisher has no certification tag. | 3/1/2026 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Fire extinguisher does not have a date tag. | 3/1/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/1/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Operating certificate shall be posted in machine room. | 3/1/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean and dry. Past Water shows at least 2 feet high. | 3/1/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | Repair or replace rusty buffer springs. | 3/1/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | repair or replace rusty pit channel | 3/1/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | repair or replace rusty governor tail sheave | 3/1/2026 |
| A17.1-2016 : Elevators | 3.20 - Governor rope | 8.10.3.2.3(u) | Yes | No | Governor rope has been exposed to water and is rusty. Shall be replaced. 30 days. | 2/26/2026 |
| A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 2.12.7 | No | No | Hoistway Access Keyswitch shall work at top and bottom landings. | |
| A17.1-2016 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.7.2.4 | Yes | No | Counterweight roller guides have been exposed to water and are rusty. Shall be replaced. | 2/26/2026 |