Inspection
Inspection Details
Equipment ID
9078
9078
Inspection Date
2/17/2020
2/17/2020
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Vincent Langendoerfer
Vincent Langendoerfer
Relief Valve Pressure
Slide
17" @ 275 FPM
17" @ 275 FPM
Governor Rope Pull
360/500
360/500
Door Closing Force
20
20
External ID
f642bbb1-d62e-48e2-a4cb-a46d2575e507
f642bbb1-d62e-48e2-a4cb-a46d2575e507
Location
Terrace Lofts
1300 CONVENTION PLZ, SAINT LOUIS, MO
Phone: (314) 621-7800
1300 CONVENTION PLZ, SAINT LOUIS, MO
Phone: (314) 621-7800
Owner
Attn: Terraceloftsrobert LLC & Terraceloft LLC & Terraceloftsrst LLC
Terraceloftsrobert LLC & Terraceloft LLC & Terraceloftsrst LLC
393 N Euclid, ste 300, St. Louis, MO 63108
Phone: (314) 761-7067 Ext: 135
Email: steve@redbrickstl.com
Terraceloftsrobert LLC & Terraceloft LLC & Terraceloftsrst LLC
393 N Euclid, ste 300, St. Louis, MO 63108
Phone: (314) 761-7067 Ext: 135
Email: steve@redbrickstl.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Repair inoperable emergency phone. | 2/17/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | x | Machine room wiring shall be enclosed. | 7/6/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | x | The machine room lighting shall not be less than 19fc at the floor level. | 7/6/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | x | An ABC type fire extinguisher shall be provided in the elevator machine room. | 7/6/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.1 - Car platform guard | 8.11.2.1.4(a) | x | Car platform guard shall be 48". | 7/6/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | x | Provide temperature and humidity control. | 7/6/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | x | Provide counterweight runby signage. Signage shall be 1" stamped, etched, or cast lettering. | 7/6/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | x | Seal all machine room penetrations. | 7/6/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | x | Seal all hoistway penetrations. | 7/6/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | x | Provide code compliant pit lighting. | 7/6/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | x | Adjust bottom hoistway access. | 7/6/2021 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 1/16/2023 | |
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Fire extinguisher is still out of date | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | The fire extinguisher has no certification tag. | |||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Fire extinguisher does not have a date tag. | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |