Inspection
Inspection Details
Equipment ID
11830
11830
Inspection Date
2/18/2020
2/18/2020
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Jason Lebegue
Jason Lebegue
Relief Valve Pressure
Slide
23" @ 442 FPM
23" @ 442 FPM
Governor Rope Pull
150/510
150/510
Door Closing Force
18
18
External ID
e9959a06-9767-4336-99c1-e4979bebf4f4
e9959a06-9767-4336-99c1-e4979bebf4f4
Location
Graybar Electric- Clayton
34 N MERAMEC AVE, CLAYTON, MO
Phone: (314) 713-3393
34 N MERAMEC AVE, CLAYTON, MO
Phone: (314) 713-3393
Owner
Graybar Electric- Clayton
34 N MERAMEC AVE, CLAYTON, MO 63105-3941
34 N MERAMEC AVE, CLAYTON, MO 63105-3941
Billing
Attn: Graybar Electric
34 N MERAMEC AVE, CLAYTON, MO 63105-3941
34 N MERAMEC AVE, CLAYTON, MO 63105-3941
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Car emergency lighting shall work. | 6/1/2018 | ||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | In car emergency telephone shall work. | 8/29/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | x | The machine room lighting shall be enclosed. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | x | All wireway and electrical device covers shall be installed. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | x | All temporary wiring shall be removed. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | x | The machine room lighting shall not be less than 19fc at the floor level. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | x | The machine room lighting shall be guarded. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | x | Provide at least one GFCI duplex receptacle in the machine room. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | x | Provide a current ABC type fire extinguisher in the machine room. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 Seismic (Earthquake protection) | 8.4.10 | x | Counterweight displacement function shall be operational. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 8.6.4.11 | x | 2.10.2.2 - An intermediate rail, member, or panel is required on the standard car top railing. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | x | Seal all penetrations in the hoistway. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | x | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Fire Fighters operation must be tested, including all recall and shunt trip devices, and an indicator light is required at the egress floor. | 3/3/2020 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | x | The main disconnects and lighting branch circuit disconnects must have feeder locations labeled. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 Seismic (Earthquake protection) | 8.4.10 | x | An identified momentary reset button or switch for each elevator, shall be located in the control panel in the elevator machine room for the counterweight displacement function. | 3/3/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | All machine room wiring shall be enclosed. | 9/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | All wireway and electrical device covers shall be installed. | 9/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | All temporary wiring shall be removed. | 9/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | The machine room lighting shall not be less than 19fc at the floor level. | 9/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | The machine room lighting shall be guarded. | 9/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Provide at least one GFCI duplex receptacle in the machine room. | 9/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | Provide a current ABC type fire extinguisher in the machine room. | 9/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 8.6.4.11 | x | 2.10.2.2 - An intermediate rail, member, or panel is required on the standard car top railing. | 4/30/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 4/29/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | A fire service indicator light is required at the egress floor. Unit undergoing MOD and not in service | 4/30/2021 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | Seal all penetrations in the hoistway. | 9/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | The main disconnects, and lighting branch circuit disconnects must have feeder locations labeled. | 9/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | (Acceptance violations that need to be re-inspected) All machine room wiring shall be enclosed, all wireway and electrical device covers shall be installed, and all temporary wiring shall be removed. | 4/29/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | (Acceptance violations that need to be re-inspected) The machine room lighting shall not be less than 19fc at the floor level and the machine room lighting shall be guarded. | 4/29/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | (Acceptance violations that need to be re-inspected) Provide at least one GFCI duplex receptacle in the machine room. | 4/29/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | (Acceptance violations that need to be re-inspected) 2.10.2.2 - An intermediate rail, member, or panel is required on the standard car top railing. | 4/29/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | (Acceptance violations that need to be re-inspected) Provide a current ABC type fire extinguisher in the machine room. | 4/29/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | (Acceptance violations that need to be re-inspected) Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 4/29/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | (Acceptance violations that need to be re-inspected) A fire service indicator light is required at the egress floor. Unit undergoing MOD and not in service | 4/29/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | (Acceptance violations that need to be re-inspected) Seal all penetrations in the hoistway. | 4/29/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | (Acceptance violations that need to be re-inspected) The main disconnects, and lighting branch circuit disconnects must have feeder locations labeled. | 4/29/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | Fire service operation shall be tested along with all initiating devices. | 4/29/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | Standby/emergency power operation of the elevator shall be tested. | 4/29/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 3/17/2023 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Building is currently under construction. About 50 feet of the hoistway shall be completed with approved materials. | 11/15/2023 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 11/15/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Emergency power must be tested annually. | 7/24/2024 |