Inspection
Inspection Details
Equipment ID
7643
7643
Inspection Date
2/21/2020
2/21/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
Not tested
Not tested
Governor Rope Pull
350/800
350/800
Door Closing Force
NA Manual Doors
NA Manual Doors
External ID
9e772dfa-4027-4d93-b6dd-85e2e13cee76
9e772dfa-4027-4d93-b6dd-85e2e13cee76
Location
Masonic Temple Association of St. Louis
3681 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 533-5460
3681 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 533-5460
Owner
Attn: UNK
3681 LINDELL BLVD
3681 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
3681 LINDELL BLVD
3681 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Billing
Attn: UNK
3681 LINDELL BLVD
3681 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
3681 LINDELL BLVD
3681 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | Yes | The cab lighting shall be operational and not less then 5fc. Elevator Red Tagged due to alarm bell and cab lighting both not working. There is no phone or intercom. | 6/5/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | The alarm bell shall be operational. Elevator Red Tagged due to alarm bell and cab lighting both not working. There is no phone or intercom. | 6/5/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room shall have permanent lighting of not less than 10 fc. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall be enclosed and accessible only to authorized personnel. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | The lighting in the stairway going up to the machine room shall be operational. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide a current tested ABC fire extinguisher in the machine room. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Car gate and hoistway doors, as well as governor pullout/pullthru, and governor switch and jaw were the only tests witnessed on 2/21/2020. All other tests required by MO CSR 40-5.090 have yet to be performed and shall be rescheduled. Other deficiencies may be noted after testing is complete. | 6/5/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room shall have permanent lighting of not less than 10 fc. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall be enclosed and accessible only to authorized personnel. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | The lighting in the stairway going up to the machine room shall be operational. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide a current tested ABC fire extinguisher in the machine room. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Car gate and hoistway doors, as well as governor pullout/pullthru, and governor switch and jaw were the only tests witnessed on 2/21/2020. All other tests required by MO CSR 40-5.090 have yet to be performed and shall be rescheduled to complete category 5 test and periodic inspection. Other deficiencies may be noted after testing is complete. | 1/25/2021 |