Inspection
Inspection Details
Equipment ID
13040
13040
Inspection Date
6/1/2018
6/1/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
50/310
50/310
Door Closing Force
20
20
External ID
Location
Merchandise Mart Apartments
1000 Washington Ave, St. Louis, MO
Phone: (314) 436-6800
1000 Washington Ave, St. Louis, MO
Phone: (314) 436-6800
Owner
Mermart LLC
911 Washington Ave, Suite 400, St. Louis, MO 63101
911 Washington Ave, Suite 400, St. Louis, MO 63101
Billing
Attn: Mermart LLC
1000 Washington Ave, , MO 63101
1000 Washington Ave, , MO 63101
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Repair inoperable emergency phone | 5/28/2019 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 4/29/2020 | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | Fire extinguisher needs to be serviced. | 8/10/2020 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 4/30/2021 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. | 6/17/2022 | |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5c Receptacles | A duplex GFCI receptacle rated at not less than 15 A, 120 V shall be provided in each machine room and machinery space. | 11/7/2023 | ||
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 11/7/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | The signage for “In Case of Fire” is missing on a number of landings. Install signage that conforms to the building code this elevator was installed to meet. | 11/7/2023 | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | |||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Remove all the non elevator related items from the elevator machine room. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Provide current year tested fire extinguisher in the elevator machine room. | |||
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | Remove oil return lines going back to the tank. Provide each piston means to collect oil in the pit. |