Inspection
Inspection Details
Equipment ID
10536
10536
Inspection Date
3/30/2020
3/30/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
24
24
External ID
a032be3e-1dfc-46c1-8685-d975ad815fb5
a032be3e-1dfc-46c1-8685-d975ad815fb5
Location
West Pine Apts
4490 W PINE BLVD, SAINT LOUIS, MO
Phone: (314) 531-4770
4490 W PINE BLVD, SAINT LOUIS, MO
Phone: (314) 531-4770
Owner
Attn: St Louis Housing Authority
St Louis Housing Authority
3520 PAGE BLVD, SAINT LOUIS, MO 63106
Phone: (000) 000-0000
Email: ayoung@habitat.com
St Louis Housing Authority
3520 PAGE BLVD, SAINT LOUIS, MO 63106
Phone: (000) 000-0000
Email: ayoung@habitat.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Phone not working | 6/21/2018 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 12/11/2019 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. The door currently does not lock securely. | 12/11/2019 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. Upon investigation, it has been determined that the last major alteration occurred on 11/23/1999. The proper code edition that this elevator was installed to is A17.1 1996. | 12/11/2019 |
| A17.1-1996 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 1001.2(b)(17) - no reinspect | No | No | A grease seal on the drive machine is leaking excessively and shall be replaced. | 12/11/2019 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 1001.2(c)(16) | No | No | A temporary construction barrier was installed in the elevator hoistway between the elevator cars. This barrier is designed for only temporary use and shall be removed from the hoistway. | 12/11/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope is rouging excessively and shall be replaced within 90 days. Re-inspection required | 5/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top needs to be cleaned | 8/19/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit and hoistway shall be cleaned of debris, oil & lint | 8/19/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm inoperable. Re-inspection required | 5/16/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are below minimum diameter. Replace suspension means | 9/5/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope has excessive rouging and needs replaced | 9/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Elevator car top needs to be cleaned | 8/19/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean debris and dirt from elevator hoistway | 8/19/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Replace leaking seal on elevator traction machine | 8/19/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell in elevator cab does not work | 9/5/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are below minimum diameter, need to replace suspension ropes. Re-inspection required | 9/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Elevator cartop needs to be cleaned | 9/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Need to clean debris and dirt from elevator hoistway | 9/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Need to replace leaking seal on elevator traction machine | 9/13/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell in elevator cab does not work. Re-inspection required | 9/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Missing ceiling tiles inside elevator. | 1/23/2025 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Hoist ropes are undersized and rouged and meet the criteria for replacement. Take corrective action as needed. | 1/17/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Emergency power tested and elevator will not take calls. Stuck on 9th floor. Take corrective action and re-test. | 1/17/2025 |
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 210.1a | Yes | No | Lobby call button is stuck and does not work. Take corrective action. | 1/17/2025 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | Yes | No | Ropes need to be shortened, counterweight runby is not sufficient, minimum 6". | 1/17/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | Yes | Phase I & Phase II fire service did not work. Elevator removed from service and Red-tagged. Re-inspection required | 4/24/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Performed test to check elevator on emergency power. After the elevator was transferred to emergency power, the elevator would not run. All operating parameters were lost in elevator controller. Repair elevator to transfer seamlessly to operate on emergency power. Re-inspection required | 4/24/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell in elevator cab does not work. Need to repair alarm bell. Re-inspection required | 4/24/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Performed test to check elevator on emergency power. After the elevator was transferred to emergency power, the elevator would not run. All operating parameters were lost in elevator controller. Repair elevator to transfer seamlessly to operate on emergency power. Re-inspection required | 3/23/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell in elevator cab does not work, needs repaired. Re-inspection required | 3/23/2026 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | Yes | No | All duct covers must be installed before 2nd elevator is turned over. | 8/17/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Yes | No | Heat and smoke detectors must be tested again before 2nd elevator is turned over. | 8/17/2026 |