Inspection
Inspection Details
Equipment ID
17345
17345
Inspection Date
2/4/2020
2/4/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
580
580
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
855c9fa7-ef1d-4106-8499-b6c44f784db5
855c9fa7-ef1d-4106-8499-b6c44f784db5
Location
Sullivan Place Apartments East
3015 N 23RD ST, SAINT LOUIS, MO
Phone: (314) 269-8000
3015 N 23RD ST, SAINT LOUIS, MO
Phone: (314) 269-8000
Owner
Cohen Esrey
6800 W 64TH ST STE 101, OVERLAND PARK, KS 66202-4179
6800 W 64TH ST STE 101, OVERLAND PARK, KS 66202-4179
Billing
Attn: Sullivan Place Apartments
3015 N 23RD ST, SAINT LOUIS, MO 63107-3091
3015 N 23RD ST, SAINT LOUIS, MO 63107-3091
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Existing cab emergency telephone does not work, and shall be repaired and tested. | 8/7/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational with 24/7 support. | 7/7/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 11/2/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/9/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 5/22/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed on the overspeed valve within 90 days. | 5/22/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/27/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. | 7/27/2023 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | A Current ABC fire extinguisher shall be provided in the machine room. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency power operation could not be tested. |