Inspection
Inspection Details
Equipment ID
9740
9740
Inspection Date
6/20/2018
6/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
Location
Apartments at Clara
605 Clara Ave, St. Louis, MO
Phone: (314) 327-2035
605 Clara Ave, St. Louis, MO
Phone: (314) 327-2035
Owner
Revival STL Construction, LLC
P O Box 46721, St. Louis, MO 63146
P O Box 46721, St. Louis, MO 63146
Billing
Attn: Revival STL Construction, LLC
P O Box 46721, , MO 63146
P O Box 46721, , MO 63146
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | No maintenance records on site | 9/19/2018 |
| conversion | conversion | n/a | No | No | Car door reopening device shall work | 9/19/2018 |
| conversion | conversion | n/a | No | No | Missing nonvision panels on hoistway doors | 9/19/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency light shall work | 5/28/2019 |
| conversion | conversion | n/a | No | No | Current state operating certificate shall be displayed | 9/19/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency phone shall work | 5/28/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The hold feature on Phase 2 fire service shall work properly. | 10/29/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The door close feature on Phase 2 fire service shall work properly. | 10/29/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The photo eye shall be bypassed on Phase 2 fire service. | 10/29/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Sight guard is missing. | 12/1/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Patch the holes in the machine room wall. | 12/1/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The smoke detector is obstructed with a rag. Remove the obstruction. | 10/29/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency phone shall work. | 10/29/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | In car emergency lights shall work. | 12/1/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)2 | No | No | Sight guards missing on hoistway doors. | 12/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 12/18/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)6 | No | No | Door reopening device (electric eye) does not work. | 12/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be provided on site. | 12/1/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Provide current state operating certificate in machine room. | 12/1/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Not on site | 4/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | No fire extinguisher in machine room | 4/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP | 4/1/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Current pit ladder is beside non running unit. Unable to access pit. Provide means. | 4/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger oil line. | 4/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide code compliant means to collect oil in pit. | 4/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Sight guard missing from 1st floor hoist way door, replace. | 4/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The current state operating certificate shall be posted in the machine room in a non-combustible frame. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Current pit ladder is beside non running unit. Unable to access pit. Provide means. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Current pit light switch is beside a non running unit. Unable to access switch. Provide means. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger oil line form the hydraulic oil tank and provide a code compliant means to collect oil in pit to record oil loss. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Sight guard missing from 1st floor hoist way door, replace. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency car lighting is not operational.The fixture shall be repaired to operate. Reinspection required. | 5/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required. | 5/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car top inspection light doesn’t operate. Repair fixture for proper operation. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Holes in Overhead shall be sealed (previously a traction elevator) | |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Hole in hoistway (pit area) to machine room shall be sealed | |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Pit ladder access is in non running unit. Unable to Access. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit Light switch is in a non running unit. Unable to Access. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit Shall be cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Sight Guard missing from 1st floor hoistway doors | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Car Emergency Light and Bell shall be repaired (bell muffled, light not working) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Car top light shall be repaired. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current operating certificate shall be posted in machine room | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car lighting shall be guarded and ceiling panels repaired | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Phase2 sign is incorrect and shall be permanently covered (engraved in COP) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Inspection key switch in COP shall be repaired |