Inspection
Inspection Details
Equipment ID
1843
1843
Inspection Date
3/17/2020
3/17/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
510
510
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
7cf6bbfe-183e-4e30-85de-f8c1b786c72e
7cf6bbfe-183e-4e30-85de-f8c1b786c72e
Location
Marquette High School
2351 CLARKSON RD, CHESTERFIELD, MO
Phone: (636) 458-7288
2351 CLARKSON RD, CHESTERFIELD, MO
Phone: (636) 458-7288
Owner
Attn: Rockwood School District
Rockwood School District
111 E NORTH ST, EUREKA, MO 63025
Phone: (000) 000-0000
Email: cobbsdevon@rsdmo.org
Rockwood School District
111 E NORTH ST, EUREKA, MO 63025
Phone: (000) 000-0000
Email: cobbsdevon@rsdmo.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Re-locate the pit light fixture to clear the elevator. | 4/24/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Relocate the pit light so that it clears the car. | 4/24/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 12/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/15/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Battery lowering device shall be operational. | 3/23/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Evacuation procedures are missing from the MCP. | 8/15/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/7/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The auxiliary power lowering operation shall be functional. | 7/10/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Battery lowering is still not working as of the 7/10/2024 re-inspection. | 3/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/7/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room shall be kept clear of all non-elevator materials. | 8/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Emergency battery lowering is not working. | 4/29/2026 |