Inspection
Inspection Details
Equipment ID
11076
11076
Inspection Date
3/26/2020
3/26/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Curtis Pelate
Curtis Pelate
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
61c679e2-8ba4-441a-ba6f-e42dfafd149c
61c679e2-8ba4-441a-ba6f-e42dfafd149c
Location
The Fulton School
123 SCHOOLHOUSE RD, SAINT ALBANS, MO
Phone: (636) 458-6688
123 SCHOOLHOUSE RD, SAINT ALBANS, MO
Phone: (636) 458-6688
Owner
The Fulton School
123 SCHOOLHOUSE RD, SAINT ALBANS, MO 63073-1211
123 SCHOOLHOUSE RD, SAINT ALBANS, MO 63073-1211
Billing
Attn: The Fulton School
123 SCHOOLHOUSE RD, SAINT ALBANS, MO 63073-1211
123 SCHOOLHOUSE RD, SAINT ALBANS, MO 63073-1211
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV not sealed. Perform test on or before next annual inspection. | 7/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide on-site written maintenance control program. | 7/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | The emergency light, bell, and phone shall all be operational. Elevator Red Tagged due to no emergency communication. | 3/31/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 3/31/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Battery lowering shall be operational. | 3/31/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve. The valve shall be sealed and tagged after the category 5 test. | 3/31/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Battery lowering shall be operational. | 4/13/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve. The valve shall be sealed and tagged after the category 5 test. | 4/13/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | RED TAGGED due to hydraulic oil leak (car will not reach the top floor and trips oil timer). | 11/20/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The entire annual inspection still needs to be completed once the oil leak is corrected. | 11/20/2025 |