Inspection
Inspection Details
Equipment ID
23719
23719
Inspection Date
1/27/2020
1/27/2020
Inspection Type
Alteration
Alteration
Inspector Name
Wendy Eiss
Wendy Eiss
Mechanic Name
Timothy Neulist
Timothy Neulist
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
4f8d4495-e191-4c26-8f20-3d4631230ef1
4f8d4495-e191-4c26-8f20-3d4631230ef1
Location
Mexico United Methodist church
122 E PROMENADE ST, MEXICO, MO
Phone: (573) 581-4791
122 E PROMENADE ST, MEXICO, MO
Phone: (573) 581-4791
Owner
Attn: United Methodist Church
United Methodist Church
122 E PROMENADE ST, MEXICO, MO 65265
Phone: (000) 000-0000
Email: office@mexicoumc.org
United Methodist Church
122 E PROMENADE ST, MEXICO, MO 65265
Phone: (000) 000-0000
Email: office@mexicoumc.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Gutter water pipes that run over controller | 3/23/2021 |
| conversion | conversion | n/a | No | No | Escape hatch needs to be bolted down from car top | 3/23/2021 |
| conversion | conversion | n/a | No | No | Pit needs permanent light fixture switch shall be accesible from pit access door | 3/23/2021 |
| conversion | conversion | n/a | No | No | Cover needed for interlock at Floor L | 3/23/2021 |
| conversion | conversion | n/a | No | No | Pit needs ladder, it shall extend 30in above the sill or provided hand grip | 3/23/2021 |
| conversion | conversion | n/a | No | No | Floor B and Floor 1 needs about 1 1/2 in spacer on hoistway door to meet allowable space requirements | 3/23/2021 |
| conversion | conversion | n/a | No | No | Pit full of oil needs to be removed | 3/23/2021 |
| conversion | conversion | n/a | No | No | Pit stop switch shall provided IAW A17.1 1995 It shall be accessible from pit access door | 3/23/2021 |
| conversion | conversion | n/a | No | No | Need 5 Gal pit bucket in pit to collect oil from overflow from head | 3/23/2021 |
| conversion | conversion | n/a | No | No | If hydraulic cylinder not replaced the packing for cylinder head needs to be replaced. | 3/23/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | No guard on car light fixture | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door not self closing or locking | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Gutter / shield pipes in machine room to protect controller | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | No pit light | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | No | No | To much space between inside hoist way door and car gate | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No "maintenance control program" records |