Inspection
Inspection Details
Equipment ID
12507
12507
Inspection Date
3/24/2020
3/24/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
320
320
Slide
Governor Rope Pull
Door Closing Force
14
14
External ID
48b997e4-1d8f-4a0b-9c1e-ec1e90425fb0
48b997e4-1d8f-4a0b-9c1e-ec1e90425fb0
Location
Four Seasons Shopping Center
42 FOUR SEASONS SHOPPING CTR, CHESTERFIELD, MO
Phone: (314) 991-8900
42 FOUR SEASONS SHOPPING CTR, CHESTERFIELD, MO
Phone: (314) 991-8900
Owner
Attn: Caplaco Management Co.
Caplaco Management Co.
PO Box 419121, St. Louis, MO 63141
Phone: (314) 991-8900 Ext: 223
Email: jc@caplaco.com
Caplaco Management Co.
PO Box 419121, St. Louis, MO 63141
Phone: (314) 991-8900 Ext: 223
Email: jc@caplaco.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be provided on site for each elevator. | 2/18/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current copy of the state operating certificate shall be displayed in the elevator machine room | 2/11/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab emergency lights do not work, Re-inspection required | 2/15/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 2/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide current tested fire extinguisher in the elevator machine room. | 2/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Determine what pipe/valve or pipe connection under the tank is leaking, repair as needed. | 2/15/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing emergency lights and bell to work. | 4/19/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Locate and repair oil leak from under pump unit and remove excess oil from pan | 4/19/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 4/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency lights do not work, needs repaired. Re-inspection required | 3/6/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Locate and repair oil leak from under pump unit and remove excess oil from pan | 3/6/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 3/6/2025 |