Inspection
Inspection Details
Equipment ID
18343
18343
Inspection Date
6/6/2018
6/6/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
Location
Express Scripts
1 Express Way, St. Louis, MO
Phone: (314) 569-4351
1 Express Way, St. Louis, MO
Phone: (314) 569-4351
Owner
Express Scripts
1 Express Way, St. Louis, MO 63121
1 Express Way, St. Louis, MO 63121
Billing
Attn: Express Scripts Inc
8455 University Place Dr. Dock #2, , MO 63121
8455 University Place Dr. Dock #2, , MO 63121
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | No | No | Auxiliary power lowering device shall be operational. | 10/5/2020 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | No | No | There is water and oil that has accumulated in the pit. Remove the oil and water from the pit and correct source of leaks. The pit shall be kept dry. | 8/14/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Auxiliary power lowering device is still not operational. Repair as needed. | 6/1/2021 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering device is not operating properly. | 6/15/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering device is not operating properly. (2nd Notice) | 7/8/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the machine room. | 8/14/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The fire service monthly testing log and oil log are not being completed. | 8/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace the faded and unreadable in-car Phase 2 fire service instructions. | 8/14/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall be operational. | 8/15/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Heat detector shall be within 24" of the sprinkler head. | 8/15/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall be operational. (2nd Notice) | 8/14/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Heat detector shall be within 24" of the sprinkler head. (2nd Notice) | 8/14/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/14/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean and dry |