Inspection
Inspection Details
Equipment ID
8433
8433
Inspection Date
3/23/2020
3/23/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
91f4de5e-4058-410e-81dc-f83bf8a93127
91f4de5e-4058-410e-81dc-f83bf8a93127
Location
Monsanto Bldg CC
700 CHESTERFIELD PKWY W, CHESTERFIELD, MO
Phone: (636) 247-4767
700 CHESTERFIELD PKWY W, CHESTERFIELD, MO
Phone: (636) 247-4767
Owner
Attn: Jeff Porterfield
CBRE-Bayer
800 North Lindbergh Blvd, St. Louis, MO 63017
Phone: (314) 694-3201
Email: jeff.porterfield.ext@bayer.com
CBRE-Bayer
800 North Lindbergh Blvd, St. Louis, MO 63017
Phone: (314) 694-3201
Email: jeff.porterfield.ext@bayer.com
Billing
Attn: Katie Kaufmann
CBRE-Bayer
P.O. Box 2086, Warren, MI 48090
Phone: (314) 694-7539
Email: katie.kaufmann.ext@bayer.com
CBRE-Bayer
P.O. Box 2086, Warren, MI 48090
Phone: (314) 694-7539
Email: katie.kaufmann.ext@bayer.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Suspension ropes shall have a data tag installed. | 3/23/2020 |
| conversion | conversion | n/a | No | No | Governor rope shall have a data tag installed. | 3/23/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | Existing car door restrictor does not work. The car door restrictor shall be repaired and tested. | 4/5/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The alarm bell shall be operational. | 8/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a current state operating certificate. | 3/17/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 1/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door restrictor shall be operational. | 1/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The governor rope shall be tagged as specified by CSR 40-5.065(L)1. | 3/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The suspension rope shall be tagged as specified by CSR 40-5.065(L)1. | 3/17/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency/standby power shall be tested. The building was not prepared to test it today. | 3/31/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The means to restrict opening of the car door shall be operational. | 3/31/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.9 - Power closing of doors or gates | 2.13.3 | Yes | No | 8.6.4.13.1 - The door close button on the main car station shall be operational. The door close button on the auxiliary car station is functioning properly. | 3/31/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power operation shall be tested. | 3/17/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency power shall be tested. |