Inspection
Inspection Details
Equipment ID
6925
6925
Inspection Date
3/30/2020
3/30/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
d74c6e49-bf8f-4ff0-b94e-fa42174e452b
d74c6e49-bf8f-4ff0-b94e-fa42174e452b
Location
Normandy Nursing Home
7301 SAINT CHARLES ROCK RD, SAINT LOUIS, MO
Phone: (314) 862-0555
7301 SAINT CHARLES ROCK RD, SAINT LOUIS, MO
Phone: (314) 862-0555
Owner
Normandy Nursing Home
7301 SAINT CHARLES ROCK RD, SAINT LOUIS, MO 63133-1737
7301 SAINT CHARLES ROCK RD, SAINT LOUIS, MO 63133-1737
Billing
Attn: Normandy Nursing Home
7301 SAINT CHARLES ROCK RD, SAINT LOUIS, MO 63133-1737
7301 SAINT CHARLES ROCK RD, SAINT LOUIS, MO 63133-1737
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The lobby door gibs need replacing. | 4/15/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 6/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 4/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 12/15/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 12/15/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 12/15/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The lighting in the machine room shall be not less than 10 foot-candles at the floor level. | 12/15/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 12/15/2023 |
| A17.1-2016 : Elevators | 2.19 Gears, Bearings, and Flexible Couplings | 8.11.2.1.2(v) | No | No | Correct the oil leaks on the hoist machine. | 12/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be kept clean. | 12/15/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Stairwell leading to machine room has insufficient lighting. It must be at least 19 foot-candles. | 12/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. They could hear the inspector, but could not establish communication. | 6/30/2025 |