Inspection
Inspection Details
Equipment ID
18771
18771
Inspection Date
2/3/2020
2/3/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
David Hussey
David Hussey
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
f85fe771-bbe0-4ddf-8d66-de2c961fa07d
f85fe771-bbe0-4ddf-8d66-de2c961fa07d
Location
Four Seasons Hotel
999 N 2ND ST, SAINT LOUIS, MO
Phone: (314) 881-2071
999 N 2ND ST, SAINT LOUIS, MO
Phone: (314) 881-2071
Owner
Attn: Dwight Buchannon
Four Seasons Hotel
999 N 2ND ST, SAINT LOUIS, MO 63102
Phone: (314) 498-8304
Email: dwight.buchannon@fourseasons.com
Four Seasons Hotel
999 N 2ND ST, SAINT LOUIS, MO 63102
Phone: (314) 498-8304
Email: dwight.buchannon@fourseasons.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 1002.3b | Yes | Yes | Sheave groove worn to gauge "C" position condition. Replace governor sheave within sixty (60) days. Did not red tag. | 2/3/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 8.11.2.1.2(q) | No | No | Repair excessive noice in drive sheave, possible bearing failure. | 2/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean pit and hoistway. | 2/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Relamp machine room lighting fixtures. | 2/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.4 Protection of Light Bulbs and Tubes | No | No | Elevator cab lights must be protected in case of breakage. Put new cover on or put protective breakage tubes over bulbs | 6/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 5/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. | 5/27/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide test: unintended movement, record results. | 5/27/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide test: ascending car, record results. | 5/27/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide Cat 5 car safety test, record slide. | 5/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work properly. | 5/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Counterweight rollers excessively noisy, replace. | 6/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 6/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Provide missing bottom door guide-8th floor (hoistway door). | 6/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | Fire tab missing on 8th floor door | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.7 Cleaning of Hoistways and Pits | No | No | Pit shall be cleaned | 3/25/2026 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.4.19.13 Broken Suspension Member and Residual Strength Detection Means | Yes | No | Noncircular elastomeric-coated steel suspension members monitor (Pulse monitor) shall function. | 3/25/2026 |