Inspection
Inspection Details
Equipment ID
10131
10131
Inspection Date
4/3/2020
4/3/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
680
680
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
0ad9eba5-b28a-43b4-8ae7-496005ac58d4
0ad9eba5-b28a-43b4-8ae7-496005ac58d4
Location
Uncle Bob's Self Storage
6557 MANCHESTER AVE, SAINT LOUIS, MO
Phone: (314) 646-1107
6557 MANCHESTER AVE, SAINT LOUIS, MO
Phone: (314) 646-1107
Owner
Sovran Acquisitions LP
6467 MAIN ST, WILLIAMSVILLE, NY 14221-5856
6467 MAIN ST, WILLIAMSVILLE, NY 14221-5856
Billing
Attn: Uncle Bob's Self Storage
6557 MANCHESTER AVE, SAINT LOUIS, MO 63139-3522
6557 MANCHESTER AVE, SAINT LOUIS, MO 63139-3522
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 2/9/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed and must have a cat 5 weight test performed | 12/1/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide existing machine room lights to work. | 2/19/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator related items from the elevator machine room. | 2/19/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide existing battery backup lowering unit to work properly. | 10/7/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 2/19/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Repair inoperative ERU device | 2/19/2026 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Supply up to date serviced fire extinguisher | 2/19/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 3.27.1 Phase I Emergency Recall Operation After Device Actuation | Yes | Yes | Car emergency stop switch not overridden | 2/19/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide existing battery backup lowering unit (ERU) to work properly. | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide current year tested fire extinguisher in the elevator machine room. | |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Provide existing emergency lights and bell to work. |