Inspection
Inspection Details
Equipment ID
2887
2887
Inspection Date
5/24/2018
5/24/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
NA
NA
External ID
2887
2887
Location
Utah Pumping Station
100 Utah, St. Louis, MO
Phone: (314) 772-3429
100 Utah, St. Louis, MO
Phone: (314) 772-3429
Owner
Metropolitan Sewer District STL
2350 Market St, St. Louis, MO 63103-2555
2350 Market St, St. Louis, MO 63103-2555
Billing
Attn: Metropolitan Sewer District
2350 Market St, , MO 63103-2555
2350 Market St, , MO 63103-2555
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Provide access to hoistway at top level | 8/21/2019 |
| conversion | conversion | n/a | No | No | Post current state certificate in machine space | 8/21/2019 |
| conversion | conversion | n/a | No | No | Repair phone in car | 8/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency phone does not work. | 4/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 10/16/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance records and electrical prints shall be provided. | 10/15/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)6 | No | Yes | Hoistway doors shall comply with A17.1 1978 | 10/16/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)9 | No | Yes | A car door or gate shall be at each entrance, at least 7' high and interlocks shall be provided. | 10/16/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Controller access cover needs to be non-combustible material. | 10/15/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate. | 10/15/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)6 | No | Yes | Hoistway doors shall comply with A17.1 1978. Red tagged until compliant. | 11/4/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)9 | Yes | Yes | Door or gate shall be at least 7" high from each landing and provided with interlocks. Red tagged elevator. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Controller access cover needs to be non-combustible material. | 11/4/2020 |