Inspection
Inspection Details
Equipment ID
20406
20406
Inspection Date
4/17/2020
4/17/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Matthew Martin
Matthew Martin
Relief Valve Pressure
140/320
140/320
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
8f8904cd-2306-4244-a27d-490614e6ffec
8f8904cd-2306-4244-a27d-490614e6ffec
Location
Hotel Ignacio
3411 Olive St, St. Louis, MO
Phone: (314) 743-1352
3411 Olive St, St. Louis, MO
Phone: (314) 743-1352
Owner
Attn: Hotel Ignacio
Hotel Ignacio
3411 Olive Street, SAINT LOUIS, MO 63103
Phone: (314) 977-4410
Email: gm@hotelignaicostl.com
Hotel Ignacio
3411 Olive Street, SAINT LOUIS, MO 63103
Phone: (314) 977-4410
Email: gm@hotelignaicostl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Water and excessive corrosion in the pit shall be addressed. | 2/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | There is excessive corrosion on the pit equipment. Remove corrosion and take corrective measures to eliminate corrosion. | 2/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Can not use machine room as storage. | 2/2/2021 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV needs to be tested with full load within 90 days. | 8/23/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Pit light does not work. Replace or repair item as needed. | 9/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | Yes | No | Pit had water in it because sump pump does not work causing major corrosion in the pit and on the pit channel. Needs to be addressed. | 8/23/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit. | 9/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Provide means to prevent ground water from entering the pit. | 9/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Provide means to prevent rust on the existing pit equipment. | 9/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide current year tested fire extinguisher in the elevator machine room. | 9/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.2.1 | No | No | Remove all non elevator related items from the elevator machine room. | 9/4/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 9/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check & repair the programming of this phone for proper operation and passenger safety. Re-inspection required |