Inspection
Inspection Details
Equipment ID
20479
20479
Inspection Date
3/16/2020
3/16/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Richard Toeniskoetter
Richard Toeniskoetter
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
fdd3daa7-8f0c-4ba2-8679-54bdf589a556
fdd3daa7-8f0c-4ba2-8679-54bdf589a556
Location
Grace Community Center
7661 MEXICO RD, SAINT PETERS, MO
Phone: (636) 970-1311
7661 MEXICO RD, SAINT PETERS, MO
Phone: (636) 970-1311
Owner
Attn: Grace Community Chapel
Grace Community Chapel
7661 MEXICO RD, SAINT PETERS, MO 63376
Phone: (636) 459-9479 Ext: 124
Email: mhoffer@gcchapel.org
Grace Community Chapel
7661 MEXICO RD, SAINT PETERS, MO 63376
Phone: (636) 459-9479 Ext: 124
Email: mhoffer@gcchapel.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | 5/4/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/18/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 3/18/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 3/18/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 6/16/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Non-elevator related items can not be stored in the machine room. | 3/18/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | Machine room lighting must be at least 19 foot candles. | 3/18/2026 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an overspeed valve. Based on the installation year of 2010, a category 5 test is due on the overspeed valve on or before the next annual inspection. | 3/18/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 2024 & 2025 PM logs not present. | 3/18/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Car door rear door restrictor shall work throughout hoistway, outside of landing zone. | 3/18/2026 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Fire service operation shall be tested and documented monthly. | 3/18/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate is expired. |