Inspection
Inspection Details
Equipment ID
13617
13617
Inspection Date
4/16/2020
4/16/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Bradley Tramel
Bradley Tramel
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
24
24
External ID
0823860e-200e-4cb7-b6c4-8a9e69488f2b
0823860e-200e-4cb7-b6c4-8a9e69488f2b
Location
Convent Gardens
4497 PERSHING AVE, SAINT LOUIS, MO
Phone: (314) 243-6126
4497 PERSHING AVE, SAINT LOUIS, MO
Phone: (314) 243-6126
Owner
The Lipton Group
9100 OVERLAND PLZ, SAINT LOUIS, MO 63114-6123
9100 OVERLAND PLZ, SAINT LOUIS, MO 63114-6123
Billing
Attn: Convent Gardens
4497 PERSHING AVE APT 107, SAINT LOUIS, MO 63108-2527
4497 PERSHING AVE APT 107, SAINT LOUIS, MO 63108-2527
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Need fire stops on all hoistway doors. | 8/15/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light shall work. | 8/12/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Key switch not working. Unable to test fire service. Re-inspection required | 5/4/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of current state operating certificate needs to be properly displayed in machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine is expired. Replace or have serviced | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Lighting in machine room shall be permanent type, wiring enclosed in conduit | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove unusual electrical equipment and related wiring in machine room above fire damper | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door shall be self closing and self locking | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Provide cover on black electrical box on side of controller | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car shall work | 11/26/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Lighting in car shall be at least 5 foot candles. Repair lighting |