Inspection
Inspection Details
Equipment ID
11691
11691
Inspection Date
4/13/2020
4/13/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
Slide
UNK
UNK
Governor Rope Pull
70/480
70/480
Door Closing Force
21
21
External ID
86c4b166-ad69-43b1-bbca-558be507899d
86c4b166-ad69-43b1-bbca-558be507899d
Location
West Park II
12647 OLIVE BLVD, SAINT LOUIS, MO
Phone: (314) 727-6664
12647 OLIVE BLVD, SAINT LOUIS, MO
Phone: (314) 727-6664
Owner
Attn: West Park II Investors, LLC c/o Medrealty, LLC
West Park II Investors, LLC c/o Medrealty, LLC
14567 N Outer 40, Ste 350, Chesterfield, MO 63017
Phone: (314) 787-7429
Email: lauren.oexeman@medrealty.com
West Park II Investors, LLC c/o Medrealty, LLC
14567 N Outer 40, Ste 350, Chesterfield, MO 63017
Phone: (314) 787-7429
Email: lauren.oexeman@medrealty.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Car door restrictor does not work. | 5/8/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 5/8/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | 8/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 8/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no state operating certificate in the machine room. | 10/12/2023 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | No | No | Non-elevator related items shall not be stored in the machine room. (HVAC materials, refrigerant, etc.) | 12/5/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | No | No | Machine room lighting shall be repaired. One or more bulbs are not working. | 12/5/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Fire service testing must be properly documented. | 12/5/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.7.2 Seizing of Rope Ends | No | No | Suspension rope tail ends shall be properly seized/banded. Electrical tape is not proper. | 12/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Counterweight runby signage needs to be updated with proper maximum allowable measurement. Currently states 22", at which the overhead deflector sheave would crush cartop handrail. | 12/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | 2.4.7.2 - Cartop refuge space needs to be properly marked to allow for 43" of refuge after counterweight full compression and car bounce calculations. | 12/5/2024 |