Inspection
Inspection Details
Equipment ID
9289
9289
Inspection Date
6/20/2018
6/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
Location
Beaumont High School
3836 Natural Bridge, St. Louis, MO
Phone: (314) 633-9103
3836 Natural Bridge, St. Louis, MO
Phone: (314) 633-9103
Owner
St Louis Board of Education
801 N, 11th St., St Louis, MO 63101
801 N, 11th St., St Louis, MO 63101
Billing
Attn: Advance Elevator Co.
P.O. Box 423, , MO 64601
P.O. Box 423, , MO 64601
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Provide correct Phase 1 fire service instructions in the lobby. | 9/17/2020 | ||
conversion | conversion | n/a | The fire extinguisher in the machine room is expired. | 9/17/2020 | ||
conversion | conversion | n/a | Remove all non-elevator related equipment from the machine room. | 9/17/2020 | ||
conversion | conversion | n/a | In car ventilation fan is broken. | 9/17/2020 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | The fire extinguisher in the machine room is expired and shall be serviced or replaced with a current extinguisher. | 9/17/2020 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | The pit shall be kept clean. Clean the pit. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | The machine room shall be kept clean. Items and materials not related to the operation or maintenance of the elevator shall not be stored in the machine room. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | The car top shall be cleaned. | |||
MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | x | The visual fire service indicator in the elevator car shall be illuminated when either phase of fire service is activated. | 4/13/2022 | |
A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 8.11.3.1.3(b) | The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel. | |||
A17.1-2016 : Elevators | 1.14 - Ventilation | 8.11.3.1.1(n) | The ventilation fan in the elevator car has been removed and shall be reinstalled for ventilation/passenger safety. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | The elevator car top shall be cleaned of dust and debris. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. | 3/22/2023 | |
MO Minimum : Elevators | (I) - Pits | (I)1 | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: Phase II did not initiate when the fireman's emergency service key was turned to the “ON” position. Reinspection in 14 days required. | 3/22/2023 |