MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2 On-Site Documentation
|
No
|
No
|
Ventilation and other equipment added and/or modified on car top shall comply with code.
|
5/18/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
The signage for “In Case of Fire Use Stairs” is missing. Install signage that conforms to the building code this elevator was installed to meet.
|
11/14/2022
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
Yes
|
No
|
The elevator hoisting ropes are not the correct type of of lay for this elevator sheave. The correct rope is of “lang lay” construction as required by the manufacture. The ropes shall be replaced with the correct ropes specified by the manufacturer. Reinspection in 60 days.
|
6/2/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
The signage for "In case of fire use stairs" is missing on several floors. Install signage that conforms to the building code this elevator was installed to meet.
|
11/14/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
The signage for "In case of Fire use Stairs" is missing, need to install signage
|
9/5/2023
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. NOTE: The units at this location are in the middle of a major alteration and emergency power shall be tested once work has been completed.
|
11/5/2025
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. NOTE: The units at this location are in the middle of a major alteration and emergency power shall be tested once work has been completed.
|
4/1/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Emergency communications failure needs to be tested when all units are completed. Re-inspection required
|
4/1/2026
|