Inspection
Inspection Details
Equipment ID
6076
6076
Inspection Date
4/7/2020
4/7/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
47
47
Governor Rope Pull
155/700
155/700
Door Closing Force
26
26
External ID
bee0fa1e-fe44-4d56-943a-1b9a49a5809c
bee0fa1e-fe44-4d56-943a-1b9a49a5809c
Location
Arch Hotel Project Owner LLC
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO
Phone: (314) 655-1234
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO
Phone: (314) 655-1234
Owner
Attn: Rick Creviston
Arch Hotel Project Owner LLC
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO 63102
Phone: (314) 342-4660
Email: Rick.creviston@hyatt.com
Arch Hotel Project Owner LLC
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO 63102
Phone: (314) 342-4660
Email: Rick.creviston@hyatt.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Written maintenance control program shall be provided on-site for each elevator. | 12/19/2022 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Pit needs to be cleaned | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Cartop needs to be cleaned | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | hoistway doors on 4th floor appears to have been replaced. Adjust door height so gibs and safety retainer properly engages sill | 2/6/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Hoistway doors on 4th floor appear to have been replaced. Reinstall door restrictors as needed | 2/6/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.2 | Hoistway doors on 4th floor appear to have been replaced. Inside of door needs to be identified with proper numbering | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | emergency light and alarm in car do not work on back up power. Repair same. Reinspection required within 30 days | 2/6/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Car top needs to be cleaned | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Hoistway door at 4th floor appears to have been replaced. Adjust door height so gibbs and safety retainer properly engages sill. Re-inspection required | 2/6/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Hoistway door at 4th floor appears to have been replaced. Re-install door restrictors as needed. Re-inspection required | 2/6/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Hoistway door at 4th floor appears to have been replaced. Inside of door needs to be identified with proper numbering. Re-inspection required | 2/6/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency generators shall be tested. Re-inspection required | 5/1/2025 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Cartop needs to be cleaned | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Hostway doors 4th floor appears to have been replaced. Adjust door height so gibbs and safety retainer properly engages sill. Re-inspection required | 5/1/2025 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Hostway doors 4th floor appears to have been replaced. Re-install door restrictors as needed. Re-inspection required | 5/1/2025 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Hostway doors 4th floor appears to have been replaced. Inside of door needs to be identified with proper numbering. Re-inspection required | 5/1/2025 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency generators shall be tested. Re-inspection required | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Prior inspection violation yet to be cleared due to issues with unit. Hoistway doors 4th floor appears to have been replaced. Adjust door height so gibbs and safety retainer properly engages sill. Re-inspection required | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Prior inspection violation yet to be cleared due to issues with unit. Hoistway doors 4th floor appears to have been replaced. Re-install door restrictors as needed. Re-inspection required | ||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Items to be tested: Finish Cat 5, slide, gov pull out/pull thru, electrical trip speed, mechanical trip speed, and crush car buffer with full load. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Prior inspection violation yet to be cleared due to issues with unit. Hostway doors 4th floor appears to have been replaced. Inside of door needs to be identified with proper numbering. Re-inspection required |