Inspection
Inspection Details
Equipment ID
6079
6079
Inspection Date
4/20/2020
4/20/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
37"
37"
Governor Rope Pull
230/750
230/750
Door Closing Force
20
20
External ID
b30954db-9874-4e39-a7a3-71f56fb52072
b30954db-9874-4e39-a7a3-71f56fb52072
Location
Arch Hotel Project Owner LLC
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO
Phone: (314) 655-1234
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO
Phone: (314) 655-1234
Owner
Attn: Rick Creviston
Arch Hotel Project Owner LLC
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO 63102
Phone: (314) 342-4660
Email: Rick.creviston@hyatt.com
Arch Hotel Project Owner LLC
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO 63102
Phone: (314) 342-4660
Email: Rick.creviston@hyatt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Replace suspension ropes - Reduced diameter and rouging | 5/1/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.3.3.3 Runby & Clearances After Reroping or shortening | x | Counterweight runby is 0". Shorten hoistway cable to maintain 6" of runby. | 5/27/2020 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean pit | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | clean cartop | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace worn guide shoes on counterweight | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace missing hoistway door gibs on 9th and 2nd floor | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Hoist ropes shall be shortened so that the car can make the final limit without compressing the buffer more than 25%. Re-inspection of ropes and retesting buffers and buffer switches required within 14 days | 4/30/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Need to replace the cover on the door operator. | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency generator testing needs to be performed. Re-inspection required | 4/30/2025 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Need to clean pit | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Need to clean car top | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Need to replace missing hoistway door gibbs on 9th & 2nd floor doors | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Re-inspection violation reported 2/6/24 has not been checked yet. Hoist ropes shall be shortened so that the car can make the final limit without compressing the buffer more than 25%. Re-inspection of ropes and retesting buffers and buffer switches required. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Emergency power operation shall be tested. | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | To finish the 5 year full load test the following items must be tested: full load slide test, gov pull-out/pull thru, electrical trip speed, mechanical trip speed, and crush car buffer with full load shall. |