Inspection
Inspection Details
Equipment ID
17397
17397
Inspection Date
5/7/2020
5/7/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
c61537ad-20df-49c2-af3f-60cbfedbbdc2
c61537ad-20df-49c2-af3f-60cbfedbbdc2
Location
St. Charles Center II
820 S MAIN ST, SAINT CHARLES, MO
Phone: (314) 441-2602
820 S MAIN ST, SAINT CHARLES, MO
Phone: (314) 441-2602
Owner
Attn: UNK
Reco Development
PO BOX 190, O FALLON, MO 63366
Phone: (314) 606-5316
Reco Development
PO BOX 190, O FALLON, MO 63366
Phone: (314) 606-5316
Billing
Attn: St Charles Center II
Reco Development
PO BOX 190, O FALLON, MO 63366
Phone: (314) 606-5316
Reco Development
PO BOX 190, O FALLON, MO 63366
Phone: (314) 606-5316
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current State certificate in machine room | 4/17/2019 |
| conversion | conversion | n/a | No | No | Provide self closing & locking machine room door | 4/17/2019 |
| conversion | conversion | n/a | No | No | Remove all non elevator storage from machine room | 4/17/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Need testing procedures in the MCP on or by 1/1/2022 | 4/4/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 9/11/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without use of a key. Note: The machine room door isn't self-closing and is incapable of being locked. | 6/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Each spring buffer shall be provided with a marking plate showing it's load rating, stroke, and the number of springs. Where the springs are removable, each spring shall be identified, and the assembly marking plate shall indicate this identification. Markings shall be made in a permanent and legible manner. | 6/12/2024 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | Yes | No | An individual data plate shall be provided and maintained for each unit. The data plate shall indicate the code to be used for inspections and test. The data plate shall indicate the code and edition in effect at the time of installation. The data plate shall also indicate the code in effect at the time of any alteration and indicate the applicable requirements of section 8.7. The data plate shall be in plain view, securely attached to each main line disconnect or controller. The data plate shall be of such material and construction that the letters and figures stamped, etched, cast, or otherwise applied to the face shall remain permanently and readily legible. The height of the letters and figures shall be not less than 0.125" | 6/12/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door to be self closing and self locking | 8/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair light on top of car | 8/1/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 8/1/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the machine room, in a noncombustible frame with a clear protective vision plate over it. | 5/12/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A current maintenance control program (MCP) shall be provided in the machine room. | 5/12/2025 |