Inspection
Inspection Details
Equipment ID
638
638
Inspection Date
5/8/2020
5/8/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
F. Scott Gibson
F. Scott Gibson
Mechanic Name
Ralph Kinnison
Ralph Kinnison
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
4d49bffa-af1a-4d2e-9e95-489d7b9e70cf
4d49bffa-af1a-4d2e-9e95-489d7b9e70cf
Location
John Knox Village- East
1201 W 19TH ST, HIGGINSVILLE, MO
Phone: (660) 584-7111
1201 W 19TH ST, HIGGINSVILLE, MO
Phone: (660) 584-7111
Owner
John Knox Village-East-Meyer Foundation
1201 W 19TH ST, HIGGINSVILLE, MO 64037-1552
1201 W 19TH ST, HIGGINSVILLE, MO 64037-1552
Billing
Attn: John Knox Village- East-Meyer Foundation
1201 W 19TH ST, HIGGINSVILLE, MO 64037-1552
1201 W 19TH ST, HIGGINSVILLE, MO 64037-1552
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-closing and self-locking | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | The Hydraulic pump unit seals appears to be leaking as well as the unit muffler bolts. This is creating an overflow of the pump oil containment pan. | 3/25/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Oil overflowed pan. Clean pan and floor | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher out of date | 3/25/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting below standard | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The hydraulic pump, valve and/muffler leaking. Repair with seals and/or tighten all fittings and bolts | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Excessive packing leakage. Replace | 3/25/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs cleaning from oil bucket overflowed because of excessive packing leakage | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not dialing out | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room has inadequate lighting | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Machine room oil pan full. Clean and repair leaks on pump ,valve or muffler. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room needs fire extinguisher |