Inspection
Inspection Details
Equipment ID
2878
2878
Inspection Date
5/24/2018
5/24/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
NA
NA
External ID
2878
2878
Location
Fillmore Pump Station
100 Fillmore, St. Louis, MO
Phone: (314) 638-5047
100 Fillmore, St. Louis, MO
Phone: (314) 638-5047
Owner
Metropolitan Sewer District STL
2350 Market St, St. Louis, MO 63103-2555
2350 Market St, St. Louis, MO 63103-2555
Billing
Attn: Metropolitan Sewer District
Accounts Payable
2350 Market St, , MO 63103-2555
Accounts Payable
2350 Market St, , MO 63103-2555
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair alarm bell in car | 5/19/2020 |
| conversion | conversion | n/a | No | No | Provide access to hoistway at top level | 5/19/2020 |
| conversion | conversion | n/a | No | No | Repair phone in car | 5/19/2020 |
| conversion | conversion | n/a | No | No | Post current state certificate by machine space | 5/19/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency phone. | 4/28/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The original access door on the controller was removed or misplaced and replaced with a combustible door .Controller Access panel must be made of a non combustible material | 8/6/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)6 | No | Yes | The current hoistway door interlock does not prevent the door from being opened when the car is away from the landing. The door shall be provided with approved interlocks. | 8/6/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The Current operating certificate shall be posted in the machine room in a non combustible frame | 8/6/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | Yes | The gate restrictor device shall be repaired so the door or gate of the car will be properly restricted and restrict the opening of the gate with the maximum of 4 inches when the car is away from a landing zone. | 9/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | There shall be maintenance records in the elevator machine room or accessible to the inspector. Shall consist of maintenance task such as callbacks, examinations, test, adjustments, and replacements | 8/6/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)9 | Yes | Yes | Door shall be equipped with interlocks. Unit red tagged until repaired. |