Inspection
Inspection Details
Equipment ID
12725
12725
Inspection Date
5/1/2020
5/1/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
3eb622a5-3c5d-4633-9cc0-2049f02e15a6
3eb622a5-3c5d-4633-9cc0-2049f02e15a6
Location
Riverbend Apartments
4720 S BROADWAY, SAINT LOUIS, MO
Phone: (314) 481-4250
4720 S BROADWAY, SAINT LOUIS, MO
Phone: (314) 481-4250
Owner
Attn: UNK
The Millennia Companies
4000 Key Tower/127 Public Square, Cleveland, OH 44114
Phone: (000) 000-0000
The Millennia Companies
4000 Key Tower/127 Public Square, Cleveland, OH 44114
Phone: (000) 000-0000
Billing
Attn: UNK
The Millennia Companies
4720 S Broadway, Saint Louis, MO 63111
Phone: (000) 000-0000
Email: emaddox@livemillennia.com
The Millennia Companies
4720 S Broadway, Saint Louis, MO 63111
Phone: (000) 000-0000
Email: emaddox@livemillennia.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Door operator belt is worn out. Replace. | 11/13/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | suspension ropes are below minimum diameter. Replace. | 11/13/2018 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | Yes | 2 of 4 hoist cables are rouged and stretched to maximum. Replace cables. Noted on 2017 report. Unit red tagged. | 11/25/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Door restrictor not working. | 11/25/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate in machine room. | 9/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | No | No | Emergency light and bell not working. | 11/25/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Clean trash out of pit. | 9/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Program hands-free phone. | 5/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor does not work. | 12/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be kept on site for each elevator. | 9/21/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | When phase 1 recall was initiated, elevator 2 remained on the 8th floor. Phase 1 fire service is not working correctly | 2/14/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean of all debris | 9/21/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not work and must be repaired and be 5 foot candle minimum | 9/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Each unit shall have a written MCP that is maintained on site | 9/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Restrictor shall restrict the door from opening when not in a door zone. Repair restrictor | 2/14/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not work and must be repaired and be 5 foot candle minimum | 7/5/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned of debris | 7/5/2023 |