Inspection
Inspection Details
Equipment ID
8475
8475
Inspection Date
5/6/2020
5/6/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Kevin Liles
Kevin Liles
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
24
24
External ID
7ba68285-875a-49ad-8ee9-9a71334e4ea1
7ba68285-875a-49ad-8ee9-9a71334e4ea1
Location
Boeing Bldg #100
MCDONNELL BLVD & AIRPORT RD, BERKELEY, MO
Phone: (314) 234-6485
MCDONNELL BLVD & AIRPORT RD, BERKELEY, MO
Phone: (314) 234-6485
Owner
Boeing Co
PO BOX 516, SAINT LOUIS, MO 63166-0516
PO BOX 516, SAINT LOUIS, MO 63166-0516
Billing
Attn: Boeing Co
PO BOX 516, SAINT LOUIS, MO 63166-0516
PO BOX 516, SAINT LOUIS, MO 63166-0516
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Door closing exceeds 30 pounds needs adjsuting | 6/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car not working | 6/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair emergency light | 11/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 11/21/2025 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | Yes | No | Ropes appear to be rubbing top of hoistway spinkler pipe. Check and take corrective action. | 1/27/2026 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Adjust 2nd floor hoistway door upthrust rollers for proper clearance. (lower gap>1") | 1/27/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | FAID recall not working properly | 1/27/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need all CAT5 test items performed except POPY nad Gov spin, Fire service 1&2, finals, ETS, NTS, and items found on 17.2 list. | 1/27/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | Yes | No | Test emergency power. | 1/27/2026 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Upper machine level guardrail is only 32" in height. shall be standard height (42") with midrail (21") and toe kick in the machine room. | 1/27/2026 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | Upper machine level lighting shall not be less than 19ftc in the machine room. | 1/27/2026 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.2.2(r) | Yes | No | Disconnects shall be labeled with location feeder breakers and function in the machine room. | 1/27/2026 |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.5 | Yes | No | All ledges greater than 4"shall be properly gaurded and/or beveled at 70deg. | 1/27/2026 |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.6 | Yes | No | Walkway at top of hoistway shall have proper standard handrail w/toekick or 70deg bevel installed. | 1/27/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | Yes | No | Test emergency power. | |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Upper machine level guardrail is only 32" in height. shall be standard height (42") with midrail (21") and toe kick in the machine room. | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | Upper machine level lighting shall not be less than 19ftc in the machine room. | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.2.2(r) | Yes | No | Disconnects shall be labeled with location feeder breakers and function in the machine room. | |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.5 | Yes | No | All ledges greater than 4"shall be properly gaurded and/or beveled at 70deg. | |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.6 | Yes | No | Walkway at top of hoistway shall have proper standard handrail w/toekick or 70deg bevel installed. |