Inspection
Inspection Details
Equipment ID
2763
2763
Inspection Date
4/28/2020
4/28/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
24
24
External ID
b51c15c5-abb3-4b12-bd26-5d79c40baf2b
b51c15c5-abb3-4b12-bd26-5d79c40baf2b
Location
McDonnell Science Bldg
4566 SCOTT AVE, SAINT LOUIS, MO
Phone: (314) 362-2907
4566 SCOTT AVE, SAINT LOUIS, MO
Phone: (314) 362-2907
Owner
Attn: UNK
WUSM
660 S EUCLID AVE, CB 8080, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Email: francisco.d.saavedra@wustl.edu
WUSM
660 S EUCLID AVE, CB 8080, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Email: francisco.d.saavedra@wustl.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Water in pit (1”) | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emer Power not tested. | 4/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 Seismic (Earthquake protection) | 8.4.10 | No | No | Ring and string operation not working. | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm not working on normal power. | 4/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | Yes | No | Emergency lights not working. | 4/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | No | No | Standby power operation has not been tested. | 5/1/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Standing water in pit. | 5/1/2026 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.4.1 | No | No | Suspension ropes not equally tensioned. | 5/1/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | No Category 5 tests performed/witnessed. | 5/15/2024 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.4.1 | No | No | Suspension ropes not equally tensioned. | 5/1/2026 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.11.3.1.3(x) | Yes | No | Suspension rope undersized. | 4/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | Emergency power indicator jewel in hall not working. | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | Emergency power indicator jewel in hall not working. | 5/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two way communication inoperable and shall be repaired or replaced. |