Inspection
Inspection Details
Equipment ID
12501
12501
Inspection Date
6/21/2018
6/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
480
480
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
26
26
External ID
12501
12501
Location
William G Gillispie Village Apts
4682 Labade, St. Louis, MO
Phone: (314) 713-5275
4682 Labade, St. Louis, MO
Phone: (314) 713-5275
Owner
St. Andrews Management
9600 Halls Ferry, Jennings, MO 63136
9600 Halls Ferry, Jennings, MO 63136
Billing
Attn: St. Andrews Management
9600 Halls Ferry, , MO 63136
9600 Halls Ferry, , MO 63136
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Sump pump, pumps water into 55 gal. drum in machjine room, not code. Needs to pump water to the outdoors | 7/31/2018 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Operating Certificate expired 2019 | 10/15/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP shall be kept in equipment room, including Testing Procedure(not present) and Fire service testing log, recorded monthly. | 10/15/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency/auxiliary lighting shall work with power loss. (REINSPECTION within 30 days) | 10/30/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and bell shall work | 10/30/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 6/3/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide a maintenance control program on site | 6/3/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Provide monthly fire service test & document on log in machine room | 6/3/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 8/11/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The auxiliary power, lowering operation shall be functional. |