Inspection
Inspection Details
Equipment ID
21256
21256
Inspection Date
5/14/2020
5/14/2020
Inspection Type
Alteration
Alteration
Inspector Name
Conde (Cache) Kinsella
Conde (Cache) Kinsella
Mechanic Name
Timothy Neulist
Timothy Neulist
Relief Valve Pressure
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
4914a100-4840-4585-8771-a980f5c4c4f7
4914a100-4840-4585-8771-a980f5c4c4f7
Location
MO Baptist Hospital-West Pavilion
3015 N NEW BALLAS, ST. LOUIS, MO
Phone: (314) 996-5412
3015 N NEW BALLAS, ST. LOUIS, MO
Phone: (314) 996-5412
Owner
Attn: MO Baptist Medical
MO Baptist Medical Center
3015 N BALLAS RD, SAINT LOUIS, MO 63131
Phone: (000) 000-0000
Email: gerald.erickson@bjc.org
MO Baptist Medical Center
3015 N BALLAS RD, SAINT LOUIS, MO 63131
Phone: (000) 000-0000
Email: gerald.erickson@bjc.org
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | First floor interlock cover is missing and shall be replaced. | 11/4/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.2.3 | x | Governor will not electrically set or reset. Governor shall be repaired and tested. | 5/29/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | x | x | Emergency fire service shall be tested. | 5/29/2019 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | Clean the car top. | 11/4/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | Provide numbering on car top. | 11/4/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Clean the pit. | 11/4/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | x | 2.4.3 - Provide counterweight runby sign in the pit. | 7/31/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | Provide missing hoistway door interlock cover at 1st floor. | 11/4/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.40 - Maintenance Records | 2.26.1.4 Inspection Operation | Provide MCP. | 11/4/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | Governor will not electrically set or reset. Governor shall be repaired and tested. (Violation not cleared from previous annual inspection) | 11/4/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Automatic return to the fire recall floor after coming off Phase 2 fire service does not work and shall be repaired. Violation corrected on 9/21/2020 and scheduled for re-inspection on 10/5/2020. | 10/5/2020 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/16/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | x | Car went down during the inspection. Two cables slipped out of the under sling. | 5/28/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | The elevator went down during the annual inspection and category 5 test. The following testing items still need to be completed: 1. Door pressure., 2. Inspection of top of car., 3. Inspection of pit., 4. Fire service., 5. Emergency power test., 6. Complete entire category 5 test. | 5/28/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency power and fire service need to be tested. | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | Emergency light does not work. | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | The pit is dirty. Clean the pit. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | In 2023 this elevator inspection was stopped due to a mechanical failure. Almost all of the annual inspection and the complete category 5 test still needed to be completed. The annual was completed 5/28/24 except for fire service and emergency power testing but the category 5 test has not been completed to date. A category 5 test need to be performed and witnessed in its entirety. |