Inspection
Inspection Details
Equipment ID
8979
8979
Inspection Date
3/19/2020
3/19/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Larry Taylor
Larry Taylor
Relief Valve Pressure
620
620
Slide
Governor Rope Pull
Door Closing Force
11
11
External ID
f6152e76-16f6-4500-b779-9dce6b2ce20d
f6152e76-16f6-4500-b779-9dce6b2ce20d
Location
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO
Phone: (816) 889-4265
1 RIVERBOAT DR, N KANSAS CITY, MO
Phone: (816) 889-4265
Owner
Attn: Harrah's Casino- NKC
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO 64116
Phone: (816) 889-7034
Email: rmurphy@harrahs.com
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO 64116
Phone: (816) 889-7034
Email: rmurphy@harrahs.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.35 - Supply Line and Shutoff Valve | 303 | No | No | replace vic couplers in the tank that are leaking oil durring normal operation | 1/10/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Perform monthly fire service test and post a log in the machine room | 7/21/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/14/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit, oil collection line had fallen out of the collection bucket, oil on the pit floor. | 7/14/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | the overspeed valve is installed backwards and needs to be installed correctly and tested. | 8/17/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state operating certificate posted in the machine room is to be updated every year | 5/18/2022 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | recovery pump in the elevator pit is not allowed per state of Missouri memo 006, replace with a bucket | 10/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Recovery pump for the hydraulic oil in the elevator pit not allowed per memo from the state, memo 006 A17.1 8.6.5.5 | 10/24/2024 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Adjust the door restrictor so it works | 11/4/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove scavenger unit from the pit | 7/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Provide updated permit in the cab or other specified location | 7/18/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | Provide fire egress signage at the 2nd floor | 7/18/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil absorbent pads from the pit floor | 7/18/2025 |
| A17.1-2016 : Elevators | 9.19 - Maintenance Records | 8.6.1.4 Maintenance Records | No | No | Provide updated maintenance task log | 7/18/2025 |
| A17.1-2016 : Elevators | 1.7 - Car door or gate | 8.6.4.13.1 Door Systems General | No | No | Replace worn car door rollers | 7/18/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Clean pit floor of oil and debris and address the source of the oil leakage | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | oil rags need to be cleaned up from under the oil cooler unit, and address the source of the oil leak | |
| A17.1-1996 : Elevators | 2.40 - Maintenance Records | 210.1d Inspection Operation. | No | No | provide updated maintenance record logs for the current year |